LAARS Heating Systems

NORMAL SEQUENCE

FAILURE TO COMPLETE EVENT CYCLE

EVENT

CONTROL FUNCTION

VERIFIED

LIGHT CONFIRMS EVENT

NO LIGHT OR

BLINKING LIGHT

ACTION FOR DIAGNOSIS

A. Power switch on.

Integrated boiler control

(S9301A).

Green "POWER" light on.

Note: If internal pump is

running unit may be in

lockout. Reset power

switch.

1. No. 120 VAC supply.

1. Read voltage betwen black & white

wires at back of (120 VAC) plug.

2. Defective 24 VAC

transformer (Check 3

AMP inline fuse).

2. Read voltage between yellow wires at

back of (VAC 24XFMR) plug.

3. Defective S9301A

module.

3 Replace S9301A module

part #2400-224.

B. Pre-purge low limit

aquastat or thermostat

calling (2-17 secs).

1. Internal pump starts.

Red "PURGE" light on

NOTE: If unit is in purge

mode without light, stack

switch is not proving air

flow.

1. Internal pump

defective or air bound.

1. Check for 120 VAC at module pins

marked "CIRCULATOR" (opposite

brown & white).

2. Low limit (HW-only),

operating control, safety

limit, system or

differential pressure

switch, stack switch.

2. Defective low limit,

operating control, safety

limit, or system

differential pressure

switch.

2. Jump control wires, one control at a

time to identify open circuit in control (no

continuity) FOR DIAGNOSIS ONLY.

3. Blower starts.

3. Defective inducer

(blower).

3. Check for 120 VAC at module pins

marked "INDUCER" (opposite gray and

white wires).

C. Ignitor heats up and

remains on (17-39

secs).

Ignitor via S9301A.

Red "IGNITOR" light on.

Red "PURGE" light off.

Blower continues to run.

Ignitor does not heat up -

look for heat up at ignitor

base.

Check for 120 VAC at pins marked

IGNR (blue wires) during "IGNITOR"

light "ON".

D. Gas valve

energized (37-43

secs).

Gas valve opens.

Red "VALVE/FLAME" light

on.

1. Stack switch does not

confirm air flow.

2. Gas valve has short.

Check for 24 VAC between orange and

yellow wires on gas valve when red

"VALVE/FLAME" light is on.

E. Ignitor off (39 sec)

Gas valve energized

(39 - 43+ sec).

Ignitor, air & gas source.

Ignitor monitors flame via

flame rectification to ground

(0.6 - 1.0 microamps).

Unit transfers to purge

12-15 seconds after

valve/flame light on and

repeats sequence.

See trouble shooting section under

"cross contamination" and "short

cycling" in service manual.

Quick Reference

T

rouble Shooter

S9301A Control Module