LAARS Heating Systems

Figure 11. Manual gas shutoff.

Figure 12. Gas orifice union.

7.

Shut off pump and disconnect from hose. Carefully

drain solution from hoses and connect city water to

lower hose to flush combustion coil. Flush for

approximately 5 minutes with city water.

8.

Remove hoses, close drain cock, close drain on

cold / return, and replace lower front panel .

9.

Remove cover from thermostatic valve and

remove tape. Replace thermostat, spring, brass

ring and valve cover, and tighten bolts.

10. Open shut off valves and purge air from petcock

at top of thermostatic valve cover.

11. Re-open gas supply and turn on main disconnect

switch to return heater to service.

5.3 Thermostat Replacement

1.

Isolate the water heater and relieve pressure.

2.

Remove the screws (4) and access cover from

the jacket top.

3.

Remove the hex head machine screws (3) from

the top of the thermostatic valve, remove the

valve top and internal parts.

4.

Install new parts (P/N 2400-130).

5.

Install new O-ring valve top and replace valve

top on valve and install and tighten screws

6.

Restore pressure to water heater, bleed air from

the petcock on the valve and restart water heater.

7.

Replace access cover.

5.4 Vent and Condensate Drain

Inspection (performed annually)

1.

Inspect the vent terminals for blockage or

restrictions.

2.

Check the condition of the internal vent fittings

and hose and replace as necessary.

3.

Check the condensate drain lines for blockage

and optional condensate pump for proper

operation.

5.5 Cleaning Combustion Chamber Coil

and/or Burner

Note: In normal operation this procedure is

seldom required. Should it prove necessary, the

following procedure is used to access the coil for

cleaning (see Figure 14).
1.

Turn off the gas and electrical power to unit and

remove covers to the unit.

2.

Remove water heater plastic exhaust assembly

by undoing the four nuts that hold the plastic

flange to the lower head. Disconnect one or more

of the rubber vent couplings above the tee, and

pull the elbow and tee out from under unit.

3.

Shut off water to the system and disconnect and

remove the water inlet connection.

Figure 13. Switch location.