Out of production – LAARS Mighty Max VW (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 12

Advertising
background image

Page 12

LAARS Heating Systems

Figure 8. Top-To-Rear Vent Collar.

Adapter Plate

Top Panel

Vent

Collar/Stack

Blank Plate

(Heater

Jacket)

Blank Plate On

Flue Collector

Blank Plate On

Heater Jacket

Top Panel

1. Removal of Blank Plate and Adapter

Plate From Heater

3. Blank Plate Placement

Over Stack Top Opening

Blank Plate

(Flue

Collector)

Vent

Collar/Stack

2. Removal of Blank Plate From

Rear of Flue Collector

4. Connecting Vent Collar/Stack

to Flue Collector

Table 7. Vent Piping Specifications (Combustion Air Exhaust).

Heater

Pipe Diameter

Max Pipe Length

Max No.

Side Wall

Side Wall

Size

of Elbows

Vent Terminal

Combustion Air

in.

mm

ft.

m

Part Number

Terminal Part Number

320M

6

152

50

15

5

D2004500

20260701

400M

7

178

50

15

5

D2004600

20260702

IMPORTANT: Maximum pipe length allowed is 50 feet (15m), regardless of the number of elbows. Maximum number of elbows allowed is 5.
Vent pipe minimum clearance from combusible surfaces is 6 inches (152mm).

OUT OF

PRODUCTION

Advertising