Out of production – LAARS Mighty Max VW (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 21

Advertising
background image

Mighty Max Volume Water Heater

Page 21

By setting the gas offset pressure and gas orifice

differential pressure according to Table 10, the correct

input rate and gas to air ratio is achieved.

3.6.3 Venturi Setup Procedure -

Natural Gas

1.

Loosen the nut on the blower shutter to allow for

adjustment. Turn the heater on so that the blower

is running and the heater is not firing. Measure

the unfired venturi differential pressure. In this

unfired condition, adjust the shutter until the

unfired venturi differential pressure is according

to Table 10, “Unfired Venturi Differential” (5.8

± .3 inches wc at sea level). If this pressure range

can not be achieved, check for blockage in the

combustion air inlet, boiler and venting system.

If there is no obvious cause contact a qualified

Laars service technician.

2.

Approximately 40 seconds after the blower starts

the gas valves will open. The heater is now

firing. If the heater is not running, check all

manual gas valves and heater safety devices.

Ensure proper gas supply pressures according to

Table 4 in Section 2.

GAS

GAS ORIFICE

UNFIRED

ELEVATION,

OFFSET

DIFFERENTIAL

VENTURI

FT

PRESSURE

PRESSURE

DIFFERENTIAL

inch W.C.

inch W.C.

inch W.C.

SEA LEVEL

+0.4

+4.0

+5.8

2000

+0.4

+3.7

+5.3

4000

+0.4

+3.4

+4.9

6000

+0.4

+3.2

+4.6

8000

+0.4

+2.9

+4.2

10000

+0.4

+2.7

+3.9

Table 10. Venturi Pressure Settings - Natural Gas.

3.

Measure the gas offset pressure. Using the

regulator only, adjust the gas offset pressure

according to the installation’s altitude in Table 10

(+0.4 inches wc. at sea level). REPLACE THE

REGULATOR CAP BEFORE TAKING GAS

PRESSURE READINGS. Turn the regulator

screw clockwise to decrease the gas offset

pressure, turn the regulator screw

counterclockwise to increase the offset.

4.

Using the toggle switch, turn the heater off. Turn

the heater back on and check the gas offset

pressure while the heater is firing. If the gas

offset pressure is not according to Table 10,

adjust the regulator as needed.

5.

Measure the gas orifice differential pressure.

This pressure must be adjusted according to

Table 10 (4.0 ± .2 inches wc at sea level). Use

the blower shutter to adjust the gas orifice

differential.

6.

By adjusting the gas orifice differential, the gas

offset pressure will change. Therefore you must

repeat steps 3-5 until the gas offset and gas

orifice differential pressures are according to

Table 10.

7.

After setting all pressures, turn the heater off and

replace each shutoff valve with the factory

installed threaded plugs. The venturi has now

been adjusted for proper operation.

3.7 Venturi Adjustment - Propane Gas

The field checkout involves measuring gas and

venturi pressures, and observing the flame through the

sight glass. If necessary, the gas input rate can be

measured by timing the gas meter.

Use a single, inclined manometer or digital

manometer with a 4.0 inch water column range. Install

shutoff valves at the gas orifice (regulator outlet) tap

(red), at the venturi inlet tap (blue) and at the venturi

throat tap (yellow). After installing the shutoff valves,

be certain they are closed (see Figure 17).

1.

With the heater off, connect the positive side of

the manometer to the shutoff valve on the venturi

inlet tap (blue). Open the shutoff valve.

2.

Loosen the nut on the blower damper to allow

for adjustment. Turn the boiler on so that the

blower is running and the heater is not firing. In

this unfired condition, adjust the damper until the

venturi inlet pressure (blue tap) is 1.2 inches

water column.

3.

Approximately 40 seconds after the blower starts

the gas valves will open. The heater is now

firing. If the heater is not running, check all

manual gas valves and heater safety devices.

Ensure proper gas supply pressures according to

the table in Section 2.

“Low” Side of

Manometer

“High” Side of

Manometer

Venturi Inlet

Tap (Blue)

Venturi Throat

Tap (Yellow)

Gas Orifice

Tap (Red)

Figure 17. Measurement of Venturi Throat Pressure
Differential - Propane Gas.

OUT OF

PRODUCTION

Advertising