Out of production – LAARS Mighty Max VW (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 8

Advertising
background image

Page 8

LAARS Heating Systems

Figure 6. Installation of Tempering Valve.

Mixing Valve

Out -
Mixed Water
For Potable Use

Hot Water

From Water Heater

or Storage Tank

Cold Water

Supply

this is essentially correct for normal water. If a higher

temperature rise is measured, flow must be increased

by changing the piping or pump.

2.7.6 Combined Space Heating/Potable

Water Heating Systems

When using the Mighty Max VW heater as a

source of heat for a combined space heating/potable

water heating system, be sure to follow the

instructions of the space heating system.

Do not use water piping, fittings, valves, pumps,

and any other components which are not compatible

with potable water.

Do not connect the heater, which will be used to

supply potable water, to any heating system or

components previously used with a nonpotable water

heating system.

Do not add boiler treatment or any chemicals to

the heating system piping, since the piping contains

water for potable use.

Do not use solder containing lead in the potable

water lines.

If the space heating system requires water

temperatures greater than the water temperature for

potable hot water use, a tempering valve (see Figure 6)

Figure 5. Water Piping Diagram.

Hot Water
To Bldg.

Thermal
Expansion
Tank

Cold

Water

Hot Water
Return From
Bldg.

NOTE: Intermittent pump must be used with EM

2

and remote temperature control.

Conventional
Tank

To Drain

Service
Valve

Pump

Mighty Max
VW Heater

To Drain

KEY

Valve

Check Valve

Gauge

or other means should be installed in the potable hot

water supply line to limit the risk of scald injury.

Some jurisdictions may require a backflow

preventer in the cold water line. In such cases, the

temperature and pressure relief valve may discharge

water due to expansion. An expansion tank approved

for potable water will eliminate this condition. Follow

the manufacturer's instructions for installation of the

expansion tank.

OUT OF

PRODUCTION

Advertising