Page 27

5.3.2 Electrical Troubleshooting
Troubleshooting procedures should only be

performed by professional service technicians

qualified in heater maintenance.

Some electrical components are wired in parallel,

so it is necessary to troubleshoot in the order that they

appear on the wiring diagram or the troubleshooting

flow chart (see Figure 19).

The following steps should be used when

troubleshooting the heater:
1.

Remove the lower front panel (see Figure 20).

2.

Turn the manual gas valve on the heater off.

3.

If the heater has locked out turn the toggle switch

off for 5 seconds then back on to reset the heater.

4.

Use the troubleshooting flow chart (Figure 19) to

determine what components and wiring should

be tested first.

5.

Test each component by checking for 24 Vac or

120 Vac entering and exiting the device. If there

is voltage entering the safety device, but none

leaving then there is an open circuit and it must

be determined why it is open. When testing

components between “MV1” of the ignition

control and the gas valve install a meter and let

the heater cycle through one complete sequence

of operation. During the sequence of operation

these safeties will only be energized for the

seven second trial for ignition.

6.

Turn the manual gas valve on the heater on and

fire the heater.

CAUTION

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.

ATTENTION

Au moment de l’entretien des commandes, mettez
des étiquettes sur tous les fils avant de les
débrancher. Des erreurs de câblage peuvent
causer un fonctionnement inadéquat et dangereux.
Vérifier que tout fonctionne bien après votre
entretien.

SECTION 6.
Parts List for Mighty Max VW Heater

6.1 General Information

To order or purchase parts for the Laars Mighty

Max VW heater, contact your nearest Laars contractor

or distributor. If they cannot supply you with what

you need, contact:

Customer Service Department

Laars Heating Systems

6000 Condor Drive

Moorpark, California, 93021

Telephone (805) 529-2000
In Canada, contact:

Customer Service Department

Laars Heating Systems

480 S. Service Road West

Oakville, Ontario, Canada L6K 2H4

Telephone (905) 844-8233

Item Description

Part Number

1.

Base Assembly

320M ........................................................... 20157801
400M ........................................................... 20157802

2.

Burner and Burner Plenum Weldment

320M ........................................................... 20268401
400M ........................................................... 20268402

3.

Venturi Assembly

320M ........................................................... 20158601
400M ........................................................... 20158602

4.

Combustion Chamber Weldment

320M ........................................................... 20159101
400M ........................................................... 20159102

5.

Gas Train Assembly

320M ........................................................... 20254901
400M ........................................................... 20254902

Gas Valve

320M, 400M ................................................ V2003900

Orifice Holder

320M, 400M ................................................ P2017500

6.

Motor, Blower

320M thru 520M Nat. & Prop. Gas ............. A2088100

7.

Electrical Controls
High limit Control ........................................... E0015900
Toggle Switch ................................................. E0109200
Indicator Light ................................................ E0071300
Fusible Link ................................................... E0099403
Transformer ................................................... E0086100
Fuse Holder ................................................... E2000300
Fuse, 2 Amp .................................................. E2043600
Flow Switch .................................................... E0013000
Burner Temperature Switch ........................... E2076100
Low Water Cutoff ........................................... E2075100
Pump Time Delay .......................................... E2077700

OUT OF