1 neotherm boiler flow and head requirements, 2 neotherm water heater flow and head requirements, Neotherm boilers and water heaters – LAARS NeoTherm NTV600 - Install and Operating Manual User Manual

Page 21

Advertising
background image

NeoTherm Boilers and Water Heaters

Page 19

SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY

UNDILUTED PROPANE

NOMINAL PIPE SIZE

@

11" W.C. INLET AND 0.5" W.C. PRESSURE DROP

SIZE

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

LENGTH

MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR

20

200

418

787

1616

2422

4664

40

137

287

541

1111

1664

3205

60

110

231

434

892

1337

2574

80

94

197

372

763

1144

2203

100

84

175

330

677

1014

1952

NOTES: 1. Follow all local and national LP gas codes for line sizing and
equipment requirements. 2. Verify that inlet gas pressure remains between
4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.

Table 6D.

EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS

NOMINAL PIPE SIZE

FITTING

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

LINEAR FEET

90° ELBOW

3.6

4.4

5.2

6.6

7.4

8.5

TEE

4.2

5.3

6.6

8.7

9.9

12

Table 6B.

SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS

NOMINAL PIPE SIZE

@

0.30" W.C. PRESSURE DROP

LENGTH

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

FT

CUBIC FEET OF GAS PER HOUR

20

92

190

350

730

1100

2100

40

130

245

500

760

1450

60

105

195

400

610

1150

80

90

170

350

530

990

100

150

305

460

870

Table 6C.

NEOTHERM

NATURAL GAS

REQUIRED

CU FT

SIZE

/ HR.

80

80

105

105

150

150

199/210 199/210

285

285

399

399

500

500

600

600

750

750

850

850

Table 6A.

TO SIZE PIPING:

Measure linear distance from meter outlet to last
boiler. Add total input of all boilers and divide by
1000 to obtain cu ft / hr required. Add total
equivalent length of fittings used according to
Table 6B. Align total length (pipe and fittings) on
left side column of Table 6C with highest cubic
feet of gas required.

Notes:

Consult and confirm with Applicable Fuel Gas
Code before beginning work. Verify gas inlet
pressure is between 4 and 13 in W.C. before
starting boiler.

SECTION 5.
Pump Requirements

5.1 NeoTherm Boiler Flow and Head

Requirements

(see Table 7)

NORMAL WATER*

Flow

H/L

Temp

Flow

H/L

Temp

Size

gpm

feet

Rise °F

lpm

m

Rise °C

150

19

57

15

72

17.4

8

199

25

28

15

95

8.5

8

285

36

33

15

98

10.1

8

399

50

35

15

189

10.7

8

500

63

28

15

239

8.5

8

600**

60

24

19

227

7.3

11

750**

68

35

21

257

10.7

12

850**

68

26

24

257

7.9

13

*Maximum water hardness of 10 grains per gallon allowed.
**

See section 6B.6 on page 30

for pump information.

Table 8. NeoTherm Water Heater Flow Data.

5.2 NeoTherm Water Heater Flow and Head

Requirements

(see Table 8)

TEMPERATURE RISE IN °F

20°F

25°F

30°F

35°F

40°F

FLOW H/L

FLOW H/L

FLOW H/L

FLOW H/L

FLOW H/L

SIZE

GPM

FT

GPM

FT

GPM

FT

GPM

FT

GPM

FT

80

7.6 14.9

6.1 10.1

5.1

7.1

4.3

5.8

3.8

4.6

105

10

23.1

8

17

6.7 12.4

5.7

9.6

5

7.6

150 14.3 28.5

11.4 19

9.5 13.6

8.1 11.2

7.1

8.8

210

20

24.1

16 16.7

13.4 11.6 11.3

9

9.9

6.9

285

27

25.5

22 17.5

18

14

15 10.5

13

8

399

39

28

31

20

25 14.5

22

11

19

9

500

48

24

38

16

32

12

27

9

24

8

600

58

44

46

31

38

22

33

18

29

15

750

72

37

58

23

48

17

41

13

36

10

850

81

33

65

22

54

15

46

10

41

8

TEMPERATURE RISE IN °C

11°C

14°C

17°C

19°C

22°C

FLOW H/L

FLOW H/L

FLOW H/L

FLOW H/L

FLOW H/L

SIZE

lpm

m

lpm

m

lpm

m

lpm

m

lpm

m

80

29

4.5

23

3.1

19

2.2

16

1.8

14

1.4

105

38

7.0

30

5.2

25

3.8

22

2.9

19

2.3

150

54

8.7

43

5.8

36

4.1

31

3.4

27

2.7

210

76

7.3

61

5.1

51

3.5

43

2.7

37

2.1

285

102

7.8

83

5.3

68

4.3

57

3.2

49

2.4

399

148

8.5

117 6.1

95

4.4

83

3.4

72

2.7

500

182

7.3

144 4.9

121 3.7

102 2.7

91

2.4

600

220 13.4

174 9.4

144 6.7

125 5.5

110 4.6

750

273 11.3

220 7.0

182 5.2

155 4.0

136 3.0

850

307 10.1

246 6.7

204 4.6

174 3.0

155 2.4

Table 7. Water Flow Requirements.

Advertising
This manual is related to the following products: