NeoTherm Boilers and Water Heaters

Page 31

Figure 25. DHW Piping, Two Heaters, One Vertical Tank.

Figure 26. DHW Piping, Two Heaters, Two Vertical Tanks.

NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate NTV DHW sensor or remote aquastat

well in lower 1/3 of tank.

3. Back flow preventer may be required - check

local codes.

4. Thermal expansion tank may be required -

check local codes.

5. Factory mounted pumps are sized for a max

pipe length of 30' total, 6-90° elbows, full pipe size.

6. Caution: Pump sizing must be based opon

water hardness at job site.

WARNING: THIS DRAWING SHOWS
SUGGESTED PIPING CONFIGURATION AND
VALVING. CHECK WITH LOCAL CODES AND
ORDINANCES FOR ADDITIONAL REQUIREMENTS.

NOTES:
1. Optional CWMU & Recirc.

line location.

2. Locate NTV DHW sensor

or remote aquastat well
in lower 1/3 of tank.

3. Back flow preventer may be

required - check local codes.

4. Thermal expansion tank may be

required - check local codes.

5. Factory mounted pumps are sized

for a max pipe length of 30' total,
6-90° elbows, full pipe size.

6. Caution: Pump sizing must

be based opon water
hardness at job site.

WARNING: THIS DRAWING SHOWS
SUGGESTED PIPING CONFIGURATION AND
VALVING. CHECK WITH LOCAL CODES AND
ORDINANCES FOR ADDITIONAL REQUIREMENTS.