6B.3 Cold Water Make-Up

The cold water make-up may be connected to the

tank or to the inlet of the boiler as shown in

Figures 23-

26.

Install back flow preventers and shut offs where

needed or required by code.

6B.4 Freeze Protection

NeoTherm heaters are not certified for outdoor

installation, so the chance of freezing is minimized. In
an event such as power outage, component failure or
other issue when freezing is likely, the heater and
system must be drained to avoid the risk of damage due
to freezing. Glycol must NOT be used in volume water
heating applications.

Figure 24. DHW Piping, One Heater, Two Vertical Tanks.

6B.5 NTV Suggested Piping Schematics

Figures 23-26

show suggested piping

configurations for NTV boilers. These diagrams are
only meant as a guide. All components or piping
required by local code must be installed.

6B.6 NTV Suggested Pumps

Possible pumps for NTV sizes 600-850 are

Grundfos model TP 40-160/2B, or for size 600 (only) is
Armstrong model E22B. See

Table 8

for water flow and

head requirements.

NOTES:
1. Optional CWMU & Recirc. line location.
2. Locate NTV DHW sensor or remote aquastat well

in lower 1/3 of tank.

3. Back flow preventer may be required - check local codes.
4. Thermal expansion tank may be required - check local codes.
5. Factory mounted pumps are sized for a max pipe length of

30' total, 6-90° elbows, full pipe size.

6. Caution: Pump sizing must be based opon water

hardness at job site.

WARNING: THIS DRAWING SHOWS
SUGGESTED PIPING CONFIGURATION AND
VALVING. CHECK WITH LOCAL CODES AND
ORDINANCES FOR ADDITIONAL REQUIREMENTS.