NeoTherm Boilers and Water Heaters

Page 37

SECTION 8.
NeoTherm Control Setup
and Operation

The NeoTherm control is an integrated electronic

control that replaces many of the individual components
found on older appliances. The control acts as the
ignition control, pump control, high limit and cascading/
lead lag control and is setup using the display on the
appliance.

MENU ITEM

DEFINITION

F or C

Selects temperature units

LBTHODLOD Outdoor reset enable/disable -

enables menu items

LBT

Low boiler setpoint during outdoor reset

see Figure 29

HOD

High outdoor temperature setpoint

see Figure 29

LOD

Low outdoor temperature setpoint

see Figure 29

RMT Add

Used for Lead/Lag (follow menus)

LL

Lead/Lag enable/disable - enables menu items

HS

Hysteresis - temp range between on/off cycles

bL

Base Load % - input rate before next boiler fires

Sd

Warm weather shut-down temperature

ASC

Anti short cycle - minutes of delay between
startup

bAC

Future use - Press DONE to exit menu.

PAS

Future use - Press DONE to exit menu.

NOTE:

When enabling/disabling functions, select "Done" and wait 30
seconds before scrolling.

Table 13. Setup Mode Parameters.

MENU ITEM

FUNCTION

RANGE

DEFAULT

Outlet water

Displays the current outlet

55-190°F

120°F

temperature

water temperature & allows
the setpoint to be adjusted

Inlet water

Displays the current inlet

temperature

water temperature

Delta T

Displays the current

temperature rise across
the heat exchanger

DHW water

Displays the current DHW

60-182°F

120°F

temperature

temperature & allows the
setpoint to be adjusted

Stack

Displays the current stack

temperature

temperature

Outdoor

Displays the current outdoor

temperature

air temperature

LL

Displays the current system 60-190°F

120°F

temperature and allows the
setpoint to be adjusted

Firing Rate

Displays an indicator of the

current firing rate based
upon fan RPM. The actual
firing rate may vary.

Table 12. User Mode Menu Structure.

Figure 31. Control Buttons on User Interface.

8.1 Display Navigation

The display is divided into three menu structures,

USER, SETUP and DIAGNOSTIC. The menu structure
and variables in each are shown in

Tables 12-14

. Once

in a particular menu structure navigation consists of
pressing the next button to scroll from item to item and
then pressing the up and down arrows to change values.

Once the value is adjusted the NEXT or DONE button
can be pressed. The DONE button returns you to the
Home screen. The NEXT button increments the display
to the next item in the menu structure.

USER mode is the home screen shown on the

control. If the display is not in USER mode wait for the
display timeout period to be reached or press the Done
button to return to the USER menu.

SETUP mode is accessed by holding the up and

down arrow keys simultaneously for 3 seconds.

DIAGNOSTIC mode is accessed by holding the

NEXT button for 3 seconds.

8.2 Ignition Control- Sequence of Events

1.

Call for heat

2.

Safety chain check

3.

Fan starts and waits to achieve prepurge RPM

MENU ITEM

DESCRIPTION

mA

Display the flame sense signal

Alert codes

Displays the current alert code

Lockout code

Displays the current lockout code

Outlet Limit

Displays outlet temperature limit

DHW limit

Displays Domestic Hot Water limit setting

Stack Limit

Displays Stack limit setting

Min. firing rate

Displays the minimum firing rate allowed

Min. forced

Allows the user to force the boiler to fire at

firing rate

the minimum firing rate

Max forced

Allows the user to force the boiler to fire at

firing rate

the maximum firing rate

Rate indicator

Displays a indicator of the firing rate based
off of the fan RPM. Actual firing rate may
vary depending upon setup.

Table 14. Diagnostic Mode Menu Structure.