PRELIMINARY HARDWARE
SETTINGS

1) Remove the instrument from its case.
2) It is necessary to set J106 according to the
desired input type as shown in the following figure.

INPUT

J106

TYPE

1-2

3-4

5-6

7-8

9-10

TC-RTD open

close

open

open

open

60 mV

open

close

open

open

open

5 V

close

open

close

open

open

10 V

open

open

close

open

open

20 mA

open

open

open

close

close

NOTE : the not used jumper can be positioned on
pin 7-9

OPEN INPUT CIRCUIT
This instrument is able to identify the open circuit
for TC and RTD inputs.
The open input circuit condition for RTD input is
shown by an "overrange" indication.
For TC input, it is possible to select overrange
indication (standard) or underrange indication set-
ting the CH101 and SH101 according to the follow-
ing table:

Overrange (STD) CH101 = close SH101 = open
Underrange

CH101 = open SH101 = close

Both pads are located on the soldering side of the
CPU card

Fig. 14