5

B) LOGIC INPUT
Safety note:
1) Do not run logic input wiring together with

power cables.

2) Use an external dry contact capable of

switching 0.5 mA, 5 V DC.

3) The instrument needs 100 ms to recognize a

contact status variation.

4) The logic inputs are NOT isolated by the

measuring input

Fig. 7 - LOGIC INPUT WIRING

This logic input allows to select the operative set
point.

logic input

op. set point

open

SP

close

SP2

C) RELAY OUTPUTS

Fig. 8 RELAY OUTPUTS WIRING
The contact rating of the OUT 2, 3 is 2A/250V AC
on resistive load.
The number of operations is 1 x 10

5

at specified

rating.
NOTES 1) To avoid electrical shock, connect

power line at the end of the wiring
procedure.

2) For power connections use No 16 AWG

or larger wires rated for at last 75 °C.

3) Use copper conductors only.
4) Don’t run input wires together with

power cables.

The relay contacts are protected by varistor against
inductive load with inductive component up to 0.5 A.

The following recommendations avoid serious
problems which may occur, when using relay
output for driving inductive loads.

14

SP / SP2

15

2

1

3

NO - OUT 3

NO - OUT 2

C - OUT 2 and 3

OUT 2

OUT 3

1604-7-1-AB.p65

5/16/00, 10:50 AM

5