LINEAR OUTPUT
This instrument is equipped with one linear output
(OUT 1) programmable as:
- main output (heating or cooling)
- secondary output (cooling)
- analog retransmission of the measured value
- analog retransmission of the operative set point.

Fig. 10 mA OUTPUT WIRING

It is an isolated analog output.
Maximum load: 500

W.

INDUCTIVE LOADS
High voltage transients may occur switching
inductive loads.
Through the internal contacts these transients
may introduce disturbances which can affect the
performance of the instrument.
For the OUT 2 and OUT 3, the internal protection
(varistor) assures a correct protection up to 0.5 A
of inductive component.

The same problem may occur when a switch is
used in series with the internal contacts as shown
in Fig. 9.

Fig. 9 EXTERNAL SWITCH IN SERIES WITH
THE INTERNAL CONTACT

In this case it is recommended to install an
additional RC network across the external contact
as show in Fig. 9

The value of capacitor (C) and resistor (R) are
shown in the following table.

The cable involved in relay output wiring must be
as far away as possible from input or communica-
tion cables.

LOAD

R

C

POWER

LINE

+

_

+

_

20 mA

6

7

OUT 1

LOAD

(mA)

<40 mA
<150 mA
<0.5

A

C

(

mF)

0.047

0.1

0.33

R

(

W)

100

22
47

P.

(W)

1/2

2
2

OPERATING

VOLTAGE

260 V AC
260 V AC
260 V AC

1604-7-1-AB.p65

5/16/00, 10:50 AM

6