LINEAR INPUT

Fig. 6 mA, mV AND V INPUTS WIRING

NOTE:
1) Don’t run input wires together with power

cables.

2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be

grounded at one side only to avoid ground loop
currents.

4) The input impedance is equal to:

< 5

W for 20 mA input

> 1 M

W for 60 mV input

> 200 k

W for 5 V input

> 400 k

W for 10 V input

RTD INPUT

Fig. 5 RTD INPUT WIRING

NOTE:
1) Don’t run input wires together with power

cables.

2) Pay attention to the line resistance; a high line

resistance may cause measurement errors.

3) When shielded cable is used, it should be

grounded at one side only to avoid ground loop
currents.

4) The resistance of the 3 wires must be the

same.

8

RTD

10

9

8

RTD

10

9

Shield

_

+

mA,

mV

or

V

9

+

_

G

mA
mV

or

V

10

9

10