Chapter 2 Power and Cooling

DC Power Systems

Note

DC input power cables must be connected to the PDU terminal studs in the proper positive
(+) and negative (–) polarity. In some cases, the DC cable leads are labeled, which is a
relatively safe indication of the polarity. However, you must verify the polarity by measuring
the voltage between the DC cable leads. When making the measurement, the positive (+)
lead and the negative (–) lead must always match the (+) and (–) labels on the PDU.

An earth ground cable is required for each fixed configuration DC PDU. We recommend that you
use at least 6-AWG multistrand copper wire. This wire is not available from Cisco Systems; it is
available from commercial cable vendors.

The ground wire cable lug should be dual-hole, as shown in

Figure 2-3

, and able to fit over M6

terminal studs at 0.625-inch (15.88-mm) centers (for example, Panduit part number LCD6-14A-L
or equivalent).

Figure 2-3

DC Earth Ground Cable Lug

Figure 2-4

shows the DC input power cables connected to the DC PDU terminal studs.

Figure 2-4

Fixed Configuration DC PDU Power Cable Connections

Crimp area

25527

2.24

0.48

0.08

0.25

0.37

0.63

End View

Ø 0.267

2 holes

All measurements in inches

1

Each set of cables (RTN and –48V/–60V) is a single VDC input.