Chapter 4 annunciator installation – Potter PFC-9000 Series User Manual

Page 17

Advertising
background image

17

PFC-9000 • 5403535 • REV G • 9/08

9.95

9.95

9.95

9.00

16.00

23.00

DWG# PFC-9000-5

CHAPTER 4 ANNUNCIATOR INSTALLATION

Annunciator Overview

The PFC-9000 may be connected in any order to three types of annunciators, liquid crystal display (LCD), light emitting diodes

(LED’s) and graphic annunciation. A maximum of 272 points can be annunciated on the LED annunciator or graphic driver.
The annunciators must be mounted in a backbox and the number of needed LED’s will determine the backbox size. Sizes are

available for one to three annunciators per backbox, and each annunciator occupies one space. The backbox must be mounted

flush on the wall utilizing either one or two electrical boxes.

The communication wiring must be two conductor twisted shielded cable from the panel or previous annunciator. A maximum

of eight RA-LCD or RA-LED32 annunciators may be connected to a PFC-9000. In addition to the communication wire, the

annunciators must be powered from the auxiliary power supply from the panel. The communcation wires and power wires must

be in seperate cables.

Note: If an existing annunciator must be replaced, the program must be reloaded into the panel for the panel to communicate with

the annunciator.

Advertising