Potter PFC-9000 Series User Manual

Page 39

Advertising
background image

39

PFC-9000 • 5403535 • REV G • 9/08

The SLC loop, the sensors and the bases are polarity sensitive. The panel will have the terminals marked for positive and negative

for both Class A and Class B. The base has three sets of terminals. Terminals number 1 and 2 are for the positive, terminals 5 and

6 are for the negative and terminals 3 and 4 are for a remote annunciation. The remote annunciation has a maximum output of 8

mAmps per base.

UL LISTED

COMPATIBLE

CONTROL

PANEL

FOR REMOTE ANNUNCIATION IF USED

ASB-6

8mA MAX.

OUTPUT

DWG# PFC-9000-24

ASB-6

The sensors will only slide onto the base one way. The “DO NOT PAINT” that is embossed on the sensor should line to the right

of the Potter on the base and turn clockwise onto the base.

COVER

POTTER

LABEL

DWG# PFC-9000-25

DO

N

OT P

AIN

T

Advertising