Potter PFC-9000 Series User Manual

Page 33

Advertising
background image

33

PFC-9000 • 5403535 • REV G • 9/08

UDACT-9100 MAIN BOARD:

P1

Ribbon Cable for connecting to Potter Fire Alarm Control Panel (FACP).

P2

RS-485 Connection for future expansion.

P3

Not used.

U18

Connector for CFG-LCD Configuration Module.

Programming the UDACT-9100

The UDACT-9100 is programmed using the CFG-LCD Configuration Tool. The tool is powered directly from the UDACT-9100

and interfaces using a ribbon cable to the U18 plug on the UDACT-9100 as displayed in the UDACT drawing. The configuration

tool utilizes an LCD display to program the account number, phone number of the receiving station, etc. The Configuration

Tool has two levels of password protection, which may be changed. In addition, the UDACT-9100 can be reset to the factory

defaults by using a jumper setting. The exact codes for programming the UDACT-9100 are included in Appendix E. Detailed

programming instructions come with the CFG-LCD Configuration Tool.

UDACT-9100 Main Board Terminal Connections

Wire the two telephone lines devices to terminals as shown.
Line 1 Input (Tip/Ring):

To the first Telephone Line via the required RJ31X Connector.

Line 1 Output (Tip/Ring):

To an optional Premise Telephone on the first Telephone Line via the required RJ31X Connector.

Line 2 Input (Tip/Ring):

To the second Telephone Line via the required RJ31X Connector.

Line 2 Output (Tip/Ring):

To an optional Premise Telephone on the second Telephone Line via the required RJ31X Connector.

Note that most Authorities Having Jurisdiction do not allow the connection of Premise Telephones. Terminal blocks are

“removeable” for ease of wiring.