Programming Analog/Addressable Devices

The PFC-9000 panel has a full line of addressable peripheral devices that may be connected to the SLC. All of the peripherals

must have the EEPROM programmed. All new devices are addressed at 127. These devices must be addressed using the

Hochiki TCH-B100 hand held programmer. Also, the sensors are analog/addressable and can be diagnosed using the hand held

programmer for their analog value. The hand held programmer is powered from a conventional 9VDC battery that is provided.

Note: Before operating the device, ensure the battery is connected and when completed with the programming disconnect the

battery. Each device must be individually and uniquely addressed in order for the PFC-9000 to operate and recognize the device

connected to the SLC loop. The ionization and photoelectric smoke sensors and the fixed temperature heat sensor simply slide

onto the programmer to be programmed.

Once the address is set on a device, mark the address on the label area on the device for future reference.

REMOTE PROGRAMMING

JACK

RED BUTTON:

STORES DISPLAYED

ADDRESS INTO

SENSOR/MODULE

LEFT GRAY BUTTON:

POWERS THE UNIT UP

AUTOMATICALLY READS ADDRESS

INCREASES ADDRESS BY 10

RIGHT GRAY BUTTON:

POWERS THE UNIT DOWN

ADVANCES ADDRESS BY ONE

DISPLAY

DWG# PFC-9000-41

Testing a Sensor

The TCH-B100 has the capability of reading the analog value of the smoke and heat sensors. Slide the sensor on to programmer

and turn the programmer on by pressing the left gray button as outlined above. Once the unit is powered up, the address will

be displayed. Press the red button and the letter “A” will appear. The analog value will then be displayed. Allow the ionization

detectors to stabalize for at least 30 seconds for an accurate reading. The programmer will continue to be updated for three

minutes or until the programmer is turned off.
The programmer has eight error codes that can be displayed if the sensor or module is having a problem reading.
Bat-On upon power-up (battery check). Also on when the battery is low. A battery is good for about 3,000 address setting operations.

E0-Attempting to set an address beyond 127

E1-Attempting to program an address with no device connected

E2-Can not fire device after power up

E3-Invalid sensor response

E4-Can not find the device program

E5-Device read error

E6-Fail during Analog value reading