0 mechanical (cont’d), 1 gas piping and pressures (cont’d), Gas connection size – Reznor UDAS Unit Installation Manual User Manual

Page 12: Sizing gas supply line, 1 gas supply and connections (cont’d)

Advertising
background image

Page 12

Gas Connection Size

All piping must be in accordance with requirements outlined in the National Fuel Gas

Code ANSI/Z223.1a (latest edition) or CSA-B149.1 and B149.2 (See Paragraph 2).

Gas supply piping installation should conform with good practice and with local codes.

Support gas piping with pipe hangers, metal strapping, or other suitable material; do

not rely on the heater to support the gas pipe.
The heater is orificed for operation with natural gas having a heating value of 1000 (±

50) BTU per cubic ft or propane gas with a heating value of 2500 (± 100) BTU per cubic

ft. If the gas at the installation does not meet these specifications, consult the factory

for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petroleum

gas or any other chemical constituents of the gas being supplied.

Install a ground joint union and manual shutoff valve upstream of the unit control sys-

tem, as shown in

FIGURE 9. Installation of a trap with a minimum 3” (76mm) drip leg

is required.
The unit is equipped with a nipple that extends outside the cabinet. The gas connection

is either 1/2” or 3/4”.
Leak-test all connections by brushing on a leak-detecting solution.

WARNING

All components of a gas supply system must be leak tested prior

to placing equipment in service. NEVER TEST FOR LEAKS WITH

AN OPEN FLAME. Failure to comply could result in personal

injury, property damage or death.

Capacity of Piping

Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

Diameter of Pipe

of

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

Pipe

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20'

92

56

190

116

350

214

730

445

1100

671

2100

1281

30'

73

45

152

93

285

174

590

360

890

543

1650

1007

40'

63

38

130

79

245

149

500

305

760

464

1450

885

50'

56

34

115

70

215

131

440

268

670

409

1270

775

60'

50

31

105

64

195

119

400

244

610

372

1105

674

70'

46

28

96

59

180

110

370

226

560

342

1050

641

80'

43

26

90

55

170

104

350

214

530

323

990

604

90'

40

24

84

51

160

98

320

195

490

299

930

567

100'

38

23

79

48

150

92

305

186

460

281

870

531

125'

34

21

72

44

130

79

275

168

410

250

780

476

150'

31

19

64

39

120

73

250

153

380

232

710

433

175'

28

17

59

36

110

67

225

137

350

214

650

397

200'

26

16

55

34

100

61

210

128

320

195

610

372

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.

Sizing

Gas

Supply

Line

6.0 Mechanical

(cont’d)

6.1 Gas Piping and Pressures (cont’d)

6.1.1 Gas Supply and Connections (cont’d)

Gas Connection (inches)

Size

Natural

Propane

30, 45, 60, 75, 100, 125, 150, 175, 200

1/2

1/2

225, 250, 300, 350, 400

3/4

3/4

Advertising