1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal. The

control checks to see that the limit switch is closed and the pressure switch is open. If

the limit switch is open, the control responds as defined in the “Abnormal Heat Cycle,

Limit Switch Operation”. If the pressure switch is closed, the control will do four flashes

on the green LED and wait indefinitely for the pressure switch to open. If the pressure

switch is open, the control proceeds to prepurge.
2) Prepurge - The control energizes the venter motor and waits for the pressure switch

to close. If the pressure switch does not close within 30 seconds of the venter motor

energizing, the control will do two flashes on the green LED. The control will leave the

venter motor energized indefinitely as long as the call for heat remains and the pres-

sure switch is open.
When the pressure switch is proven closed, the control begins the prepurge time. If

flame is present any time while in prepurge, the prepurge time is restarted. If flame

is present long enough to cause lockout, the control responds as defined in “Fault

Modes, Undesired Flame”.
The control runs the venter motor for a 20 second prepurge time, then proceeds to the

ignition trial period.
3) Ignition Trial Period - The control energizes the spark and main gas valve. The

venter remains energized. If flame is sensed during the first 16 seconds, the spark is

de-energized and the control proceeds to heat fan/blower on delay. If flame has not

been sensed during the first 16 seconds, the control de-energizes the spark output

and keeps the gas valve energized for an additional one second flame proving period.

If flame is not present after the flame proving period, the control de-energizes the gas

valve and proceeds with ignition re-tries as specified in “Abnormal Heat Cycle, Ignition

Retry”. If flame is present, the control proceeds to the fan/blower on delay.
4) Fan/Blower On Delay - The control waits for 30 seconds from the time the gas

valve opened and then energizes the fan/blower motor. The gas valve and venter

motor remain energized. The control proceeds to steady heat mode.
5) Steady Heat - Control inputs are continuously monitored to ensure limit and

pressure switches are closed, flame is established, and the thermostat call for heat

remains. When the thermostat call for heat is removed, the control de-energizes the

gas valve and begins post-purge and fan/blower off delay timing.

This heater is equipped with a direct spark integrated control module (circuit board).

The module monitors the safety devices and controls the operation of the fan and ven-

ter motors and the gas valve between heat cycles.

8.3 Ignition System

Control Status - Green LED Codes

Steady ON ..........Normal Operation, No call for heat

Fast Flash ...........Normal Operation, Call for heat

1 Flash ................System Lockout, Failed to detect or

sustain flame

2 Flashes ............Pressure Switch Did Not Close within 30

Seconds of Venter motor

3 Flashes ............High Limit or Flame Rollout Switch Open

4 Flashes ............Pressure switch is closed before venter

motor is energized

Steady OFF ........Blown Fuse, No Power, or Defective Board

Flame Status - Yellow LED Codes

Steady ON ....... Flame is sensed
Slow Flash ....... Weak flame (current below 1.0

microamps ±50%)

Fast Flash ........ Undesired Flame (valve open and no

call for heat)

FIGURE 16 – DSI Integrated Control Module (circuit board)

LED Lights

LED lights are visible through a viewport on Separated Combustion Models. Remove door panel

to view LED lights on Standard Power Vent Models.

Normal Heat

Cycle Operating

Sequence

LED lights are visible

through viewport on

Separated Combustion

Models. Remove door

panel to view LED lights

on Standard Power Vent

Models.

Spark

Transformer

Control

Plug

Fuse

Thermostat

Connections

Status

Lights