0 controls and operation (cont’d), 3 ignition system (cont’d) – Reznor UDAS Unit Installation Manual User Manual

Page 24

Advertising
background image

Page 24

6) Post Purge - The venter motor output remains on for a 45-second post-purge period

after the thermostat is satisfied.
7) Fan/Blower Off Delay - The fan/blower motor is de-energized after a fan/blower off

delay (120 seconds). Timing begins when the thermostat is satisfied.

Interrupted Thermostat Call for Heat - If the thermostat demand for heat is removed

before the flame is recognized, the control will run the venter motor for the post purge

period and de-energize all outputs.
If the thermostat demand for heat is removed after successful ignition, the control will

de-energize the gas valve, run the venter motor through post purge, and run the fan/

blower motor on heat speed for the selected delay off time.
Ignition Retry - If flame is not established on the first trial for ignition period, the control

de-energizes the gas valve and the venter motor remains energized for an inter-purge

period of 10 seconds. The spark and gas valve are then re-energized, and the control

initiates another trial for ignition.
If flame is not established on the second trial for ignition, the control de-energizes the

gas valve, energizes the fan/blower motor on heat speed, and venter motor remains

energized. The fan/blower motor is shut off after 120 seconds. When the fan/blower

motor de-energizes, the spark and gas valve are re-energized and the control initiates

another trial for ignition. (This fan delay is self-healing feature for an open auxiliary limit

switch).
If flame is not established on the third trial for ignition period, the control de-energizes

the gas valve, and the venter motor remains energized for an inter-purge period of 10

seconds. The control then re-energizes the gas valve and spark and initiates another

trial for ignition.
If flame is not established on the fourth trial for ignition (initial try plus 3 re-tries), the

control de-energizes the gas valve and goes into lockout. The control goes to one flash

on the green LED to indicate ignition failure lockout.
Limit Switch Operation - The limit switch is ignored unless a call for heat is pres-

ent (W energized). If the limit switch is open and a call for heat is present, the control

de-energizes the gas valve and turns the fan/blower motor on heat speed and runs

the venter motor. The control will be in soft lockout and flashing fault code “3” before

returning to normal operation.

When the switch re-closes or the call for heat is lost, the control runs the venter motor

through post purge and runs the blower/fan motor through the selected fan off delay.
Pressure Switch - If the pressure switch opens before the trial for ignition period, the

venter motor will run through the pressure switch recognition delay (2 seconds), the

gas valve will be de-energized, and the venter motor will run through the postpurge

time. The control will re-start the heat cycle at the pressure switch proving state if the

call for heat still exists.

Pressure switch opening for less than 2 seconds during the trial for ignition period shall

not interrupt the heat cycle. (Gas valve will de-energize while the pressure switch is

open.)

If the pressure switch opens after a successful ignition, the control will de-energize

the gas valve. If flame is lost before the end of the 2 second pressure switch recogni-

tion delay, the control will respond to the loss of flame. If the pressure switch remains

open for 2 seconds and the flame remains, the control de-energizes the gas valve, the

venter motor runs through post-purge, and the fan/blower motor runs on heat speed

through the selected fan off delay. When the fan off delay is over, the fan/blower motor

is de-energized, and a heat cycle is begun if the call for heat still exists.

When the thermostat calls for continuous fan (G) without a call for heat, the fan motor is

energized after a .25 second delay. NOTE: This brief on delay is to allow the “G” termi-

nal to energize slightly before “Y” and an external changeover relay to switch from “G”

to “W” without causing momentary glitches in the fan/blower output. The fan remains

energized as long as the call for fan remains without a call for heat.

Abnormal Heat Cycle

Functions

8.3 Ignition System

(cont’d)

8.0 Controls and

Operation

(cont’d)

Normal Heat Cycle Operating Sequence (cont’d)