FIGURE 12 - Supply

Wiring Connections at

the Circuit Board (DSI

Integrated Control

Module)

Supply Wiring

Connections

NOTE: Circuit

board is polarity

sensitive; “hot”

wire MUST BE

connected to

Terminal L1.

See section

10.3

Troubleshooting

on pages 36&37

for symptoms.

For all models, the terminal strip for 24 volt thermostat connections is located on the

outside of the cabinet at the back of the heater (See

FIGURE 13). Wires from the ter-

minal strip are factory wired to the circuit board.

7.3 24V Control

Wiring

Connections

Spark

Transformer

Control

Plug

Fuse

Thermostat

Connections

Status

Lights

x

7.2 Supply Wiring

Check the rating plate on the heater for the supply voltage and current requirements.

A dedicated line voltage supply with disconnect switch should be run directly from the

main electrical panel to the heater. All external wiring must be within approved conduit

and have a minimum temperature rise rating of 60°C

.

Conduit must be run so as not

to interfere with the heater access panel. If the installation requires a stepdown trans-

former (Option CG - on some models), follow the instructions shipped with the option

package for attaching the transformer to the heater.
The electrical supply enters at the rear of the heater (See

FIGURE 13). Separated

Combustion Models include a built-in disconnect switch (20A @ 115V; 10A @ 230V

Rating). The Separated Compustion Model supply wiring connects to leads located

inside a sealed electrical box. To maintain the sealing feature of the electrical box,

always replace the cover plate. The Standard Power Vent Model supply wiring con-

nects directly to leads on the integrated circuit board.
The circuit board (See

FIGURE 12) is located inside on the bottom of the control com-

partment. The circuit board is polarity sensitive. It is advisable to check the electrical

supply to be certain that the black wire is the “hot” wire and that the white wire is the

neutral wire. The supply connection made to “L1” on the circuit board must be the “hot”

wire.

FIGURE 13 - Terminal

Strip for 24-volt wiring

is on the outside rear of

the heater.

Rear View Standard

Power Vent Model

Rear View Separated

Combustion Model

NOTE: The size of heater

illustrated has a vertical

terminal strip. Some sizes

have a horizontal terminal

strip.