0 dimensions and clearances, 1 dimensions, 2 clearances – Reznor EEDU Unit Installation Manual User Manual

Page 7: Figure 4c - front view of coupled furnaces, Figure 4d - top view of coupled furnaces, Figure 5 - model eedu dimensions - inches (mm)

Advertising
background image

Form I-EEDU, P/N 150492 R6, Page 7

FIGURE 4C - Front View of Coupled Furnaces

A

A + 2"

(51mm)

Limit

Control

Limit

Control

Size

"A"

75-100

14-5/8"

371mm

125-140 17-3/8"

441mm

170

20-1/8"

512mm

200

22-7/8"

581mm

225

25-5/8"

651mm

250

28-3/8"

721mm

300

33-7/8"

860mm

350

39-3/8" 1000mm

400

44-7/8" 1140mm

FIGURE 4D - Top View of Coupled

Furnaces

(NOTE: Access panel may be in top or

bottom of ductwork.)

Access panel for

limit control service

and observation of

coupled units.

Limit Control

(Discharge Duct)

4.0 Dimensions and Clearances

D

M

3-1/2 (89)

Limit Control

J (Duct Width)

4(102) Minimum Unit S

pacing

Combustion Air Openings

of Hangers

16 (406)

5 (127)

K

L

C

6-3/4

(171)

18 (457)

Duct

Height

8-1/8

(206)

3/4

(19)

AIR

FLOW

26”

660mm

3-1/2

(89)

4-1/4

(108)

29 (737)

KEEP CLEAR

FOR SERVICE

B

Combustion

Air Opening

H

Electric Supply

REAR VIEW

SIDE VIEW

FRONT VIEW

A

CL

F

E

G (Gas Connection)

View port

(both sides)

C of Hangers

L

3/4

(19)

FIGURE 5 - Model EEDU Dimensions - inches (mm)

4.1 Dimensions

Size

A

B

C

D

E

F

G-Nat G-Pro

H

J

K

L

M

Dimensions- inches

75, 100

35

14-1/4

35-11/16

14-5/8

4-3/8

3-15/16

1/2

1/2

5/8

12-1/2

7-1/4

7-7/16

4-5/8

125, 140

35

17

35-11/16

17-3/8

4-3/8

3-15/16

1/2

1/2

5/8

15-1/4

7-1/4

7-7/16

6

170

35

19-3/4

35-11/16

20-1/8

4-3/8

3-15/16

1/2

1/2

5/8

18

7-1/4

7-7/16

7-3/8

200

35

22-1/2

35-11/16

22-7/8

4-3/8

3-15/16

1/2

1/2

5/8

20-3/4

7-1/4

7-7/16

8-3/4

225

35-3/4

25-1/4

35-11/16

25-5/8

4-3/8

4-15/16

1/2

1/2

1-3/8

23-1/2

7-1/4

7-7/16

10-1/8

250

35-3/4

28

35-11/16

28-3/8

7-1/8

4-15/16

1/2

1/2

1-3/8

26-1/4

7-1/4

7-7/16

11-1/2

300

36

33-1/2

38-1/8

33-7/8

9-7/8

5-15/16

3/4

1/2

1-3/8

31-3/4

9-9/16

7-5/8

13-7/8

350

36

39

38-1/8

39-3/8

12-5/8

5-15/16

3/4

1/2

1-3/8

37-1/4

9-9/16

7-5/8

16-5/8

400

36

44-1/2

38-1/8

44-7/8

15-3/8

5-15/16

3/4

1/2

1-3/8

42-3/4

9-9/16

7-5/8

19-3/8

Dimensions - mm

75, 100

889

362

906

371

111

100

13

13

16

318

184

189

117

125, 140

889

432

906

441

111

100

13

13

16

387

184

189

152

170

889

502

906

511

111

100

13

13

16

457

184

189

187

200

889

572

906

581

111

100

13

13

16

527

184

189

222

225

908

641

906

651

111

125

13

13

35

597

184

189

257

250

908

711

906

721

181

125

13

13

35

667

184

189

292

300

914

851

968

860

251

151

19

13

35

806

243

194

352

350

914

991

968

1000

321

151

19

13

35

946

243

194

422

400

914

1130

968

1140

391

151

19

13

35

1086

243

194

492

Unit must be installed so that clearances are provided for combustion air space, ser-

vice and inspection, and for proper spacing from combustible construction. Clearance

to combustibles is defined as the minimum distance from the heater to a surface or

object that is necessary to ensure that a surface temperature of 90°F above the sur-

rounding ambient temperature is not exceeded. See table on top of page 8.

4.2 Clearances

NOTE: See FIGURES 5

and 7 for illustrations of

service clearances.