0 controls (cont’d), 5 controller display menus (cont’d), Service menu (cont’d) – Reznor ZQYRA Unit Installation Manual User Manual

Page 38

Advertising
background image

Form I-ZQYRA P/N 260414R5, Page 38

Control Display Description

Range

Factory Default

- - Manual Test Menu - -

Test Time Remaining: There is a 3 hour limit for the Manual Test. If more time is needed, press Prg

button any time to reset it back to 3 hours.

SaF: Supply Air Fan Status

ExF: Exhaust Air Fan Status

Fan Relay: Supply Air and Exhaust Air Fan Command

On/Off

Off

SaFanSpdSetpt: Supply Air Fan Speed Command

0-100%

18%

SaFan Vdc: Output Voltage to Supply Air Fan

ExFanSpdSetpt: Exhaust Air Fan Speed Command

0-100%

29%

ExFan Vdc: Output Voltage to Exhaust Air Fan

OA Temp: Outside Air Temperature

ER Wheel: Energy Recovery Wheel Command

On/Off

Off

ERWheel Temp: Energy Recovery Wheel Discharge Temperature

Unit DA Temp: Unit Discharge Air Temperature

↓ Next

Next menu

Page 3: (Shown only when Test Mode is set to Manual.):

HP Mode: Heat Pump Mode Command

Off/Heat/Cool

Off

HP Enable: Heat Pump Command (HP Mode should be set first)

On/Off

Off

HP Cmd Output: Heat Pump Modulation Output Percentage

0-100%

0%

HP Volts (Vdc): Modulation Output Voltage

OA Temp: Outside Air Temperature

ER Wheel Temp: Energy Recovery Wheel Discharge Temperature

Unit DA Temp: Unit Discharge Air Temperature

↓ Next

Next menu

Page 4: (Shown only when Test Mode is set to Manual. Fan Relay is set to ON and HP Enable is set to OFF.):

Suppl Heat: Supplement Heat Command

On/Off

Off

Unit DA Temp: Unit Discharge Air Temperature

Off

Page 2: (Shown only when Test Mode is set to Auto.)

- - Auto Test Status - -

Testing: Current Testing (None / Fans / ER Wheel / HP Cool / HP Heat / Preheat)

SaFan Speed: Supply Air Fan Speed Command

ExFan Speed: Exhaust Air Fan Speed Command

HP Output (%): HP Modulation Output Command

HP Volts (Vdc): Modulation Output Voltage

OA Temp: Outside Air Temperature

ER Wheel Temp: Energy Recovery Wheel Discharge Temperature

Unit DA Temp: Unit Discharge Air Temperature

↓ Next

Next menu

Page 3: (Shown only when Test Mode is set to Auto.)

Fan Relay: Fan Relay Command

SaFan Speed: Supply Air Fan Speed Command

EaFan Speed: Exhaust Air Fan Speed Command

ER Wheel: Energy Recovery Wheel Command

Reversing Valve: Reversing Valve Command

HP (%): HP Modulation Output Command

PreHeat: Preheat Command (Only shown when installed and activated)

↓ Menu Top

Returns to the top of the menu

6B. Input/Output Menu

Use up or down arrow button to see the reading or status of each item. Press the Esc button to get back to the Service Menu.

Control Display

Description

Range

- - I/O Menu - -

Page 1:

Analog Inputs

B1 Zone Temp: Unit Zone Temperature

B2 Unit DAT: Unit Discharge Air Temperature

B3 OA Temp: Outside Air Temperature

B4 ERW Temp: Energy Recovery Wheel Discharge Air Temperature

B5 ERW Hum: Energy Recovery Wheel Discharge Air Humidity

↓ Next

Next menu

Page 2:

↑ Prev

Previous menu

B6 VOC/CO2: Not Used

B7 Suction Temp: Not Used

↓ Next

Next menu

Page 3:

↑ Prev

Previous menu

Binary Inputs

DI1 SaFan Sw: Supply Fan Air Proving Switch used to provide fan status.

Off/On

6. SERVICE MENU (cont’d)

6A. Test Menu (cont’d)

8.0 Controls

(cont’d)

8.5 Controller Display Menus (cont’d)