Alarm help menu – Reznor ZQYRA Unit Installation Manual User Manual

Page 49

Advertising
background image

Form I-ZQYRA P/N 260414R5, Page 49

Page 2: (Shown only when Unit DAT Fail is selected)

--Alarm Help--

Unit Discharge Air Temperature sensor has failed. NOTE: Heat

pump will not operate with a failed unit.

↓ More

More Items

Page 3:(Shown only when Unit DAT Fail is selected)

--Alarm Help--

Discharge Air Temp Sensor. Sensor reading of -60 = open circuit

and a reading of 225 = shorted circuit.

↓ More

More Items

Page 4:(Shown only when Unit DAT Fail is selected)

--Alarm Help--

1. Verify sensor wire integrity.

2. Verify sensor resistance (See APPENDIX page 70).

↓ More

More Items

Page 5:(Shown only when Unit DAT Fail is selected)

--Alarm Help--

3. See Paragraph 10.0 for more troubleshooting info.

4. Replace sensor.

5. Contact technical support: 800-695-1901

↓ Menu Top

Returns to the top of the menu (Page 2)

Press the Esc button to go Menu page 1

Page 2:(Shown only when OAT Fail is selected)

--Alarm Help--

The Outside Air Temperature sensor has failed. Sensor reading

of -60 = open circuit and a reading of 225 = shorted circuit.

↓ More

More Items

Page 3:(Shown only when OAT Fail is selected)

--Alarm Help--

1. Verify sensor wire integrity.

2. Verify sensor resistance (See APPENDIX page 70).

↓ More

More Items

Page 4:(Shown only when OAT Fail is selected)

--Alarm Help--

3. See Paragraph 10.0 for more troubleshooting info.

4. Replace sensor.

5. Contact technical support: 800-695-1901

↓ Menu Top

Returns to the top of the menu (Page 2)

Press the Esc button to go to page 1

Page 2: (Shown only when ER Wheel Temp Fail is selected)

--Alarm Help--

ER Wheel Discharge Air Temperature sensor has failed. Sensor

reading of -60 = open circuit and a reading of 225 = shorted

circuit

↓ More

More Items

Page 3:(Shown only when ER Wheel Temp Fail is selected)

--Alarm Help--

1. Verify sensor wire integrity.

2. Verify sensor resistance (See APPENDIX page 70).

↓ More

More Items

Page 4: (Shown only when ER Wheel Temp Fail is selected)

--Alarm Help--

3. See Paragraph 10.0 for more troubleshooting info.

4. Replace sensor.

5. Contact technical support: 800-695-1901

↓ Menu Top

Returns to the top of the menu (Page 2)

Press the Esc button to go to menu page 1

Page 2: (Shown only when ER Wheel Hum Fail is selected)

--Alarm Help--

ER Wheel Discharge Air Humidity sensor has failed. System sets

default reading to 100%.

↓ More

More Items

Page 3: (Shown only when ER Wheel Hum Fail is selected)

--Alarm Help--

1. Verify sensor wire integrity.

2. Verify dc voltage (0-5vdc) from sensor.

↓ More

More Items

Page 4: (Shown only when ER Wheel Hum Fail is selected)

--Alarm Help--

3. See Paragraph 10.0 for more troubleshooting info.

4. Replace sensor.

5. Contact technical support: 800-695-1901

↓ Menu Top

Returns to the top of the menu (Page 2)

Press the Esc button to go to page 1

Page 2: (Shown only when VOC/CO2 Alarm is selected)

--Alarm Help--

VOC/CO2 Reading is above the alarm setpoint.

Press the Esc button to go to menu page 1

Page 2: (Shown only when SA Fan Fail is selected)

--Alarm Help--

The Supply Air Fan is commanded “ON” but there is no status

from the pressure switch. "ON" status is shown with a closed

contact on DI-1

↓ More

More Items

Page 3: (Shown only when SA Fan Fail is selected)

--Alarm Help--

First Reset Unit! If Fan does not start:

1. Verify “ON” command from controller.

↓ More

More Items

Page 4: (Shown only when SA Fan Fail is selected)

--Alarm Help--

2. Verify contactor is closed.

3. If OA Damper is installed, verify end switch is closed.

↓ More

More Items

Page 5: (Shown only when SA Fan Fail is selected)

--Alarm Help--

4. See Paragraph 10.0 for more troubleshooting info.

5. Contact technical support: 800-695-1901

↓ More

More Items

Page 6: (Shown only when SA Fan Fail is selected)

Control Display

Description

Page 1:

--Alarm Help--

Unit DAT Fail

Opens The Unit Discharge Air Temperature Failure Help

OAT Fail

Opens The Outside Air Temperature Failure Help

ER Wheel Temp Fail

Opens The Energy Recovery Wheel Discharge Air Temperature Failure Help

ER Wheel Hum Fail

Opens The Energy Recovery Wheel Discharge Air Humidity Failure Help

VOC/CO2 Alarm

Opens the VOC/CO2 Alarm Help

SA Fan Fail

Opens the Supply Air Fan Failure Help

EA Fan Fail

Opens the Exhaust Air Fan Failure Help

HP General Alarm

Opens the Heat Pump General Alarm Help

4way Valve Fail

Opens the Changeover Solenoid Valve Failure Help

Hi OAT Lockout

Opens the High Outside Air Temperature Lockout Help

Dirty Filter Alarm

Opens the Dirty Filter Alarm Help

Shutdown DI Alarm

Opens the Shutdown DI Alarm Help

System Restart

Opens the System Restart Help

Unit Lockout Alarm

Open the Unit Lockout Alarm Help

Low Limit Alarm

Opens the Low Limit Alarm Help

Cripple Mode Alarm

Open the Cripple Alarm Help

Wheel Maintenance

Open the Energy Recovery Wheel Maintenance Help

BAS Shutdown Alarm Opens the BAS Shutdown Alarm Help

↓ Menu Top

Returns to the top of the menu

12. ALARM HELP MENU

To access a certain menu, use the up or down arrow button. At the selected menu, press the enter button. Use the Esc button to get

back to the Main Menu.