Iii before installing – Crown Boiler KSZ175 User Manual
Page 5
3
taBlE 1a: GEnEral SPEcIFIcatIOnS
Notes:
1. Net Ratings are based on piping and pick-up allowances of 1.333.
2. Burner Capacity Rating, GPH is based on #2 oil with a Gross Heating
Value equal to 140000 BTU/Gal.
3. Maximum Working Pressure, Steam -15 PSI.
4. Tankless heater ratings based on 40F inlet water, 140F outlet water, and 190F
boiler water. Ratings are also based on 5 minute intermittent draws with 10 minutes
between draws.
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance
with this manual and the requirements of the authority having jurisdiction.
•
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of Installation of Oil Burning Equipment (ANSI/NFPA31).
•
Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having
jurisdiction, Part VI of this manual, and
ANSI/NFPA31 for additional information on venting requirements.
Power (“Side Wall”) Venting - Important note
Two problems arise when any oil-fired appliance is power vented:
1. There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc.
2. There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke
level. This can happen for many reasons, some of which are out of the control of both the installer and appliance
manufacturer.
Crown Boiler Company recommends the use of a chimney to vent the KSZ series boilers. If a power venter must be used, it
is the responsibility of the installer and power vent manufacturer to “engineer” the power vent system. crOWn BOIlEr
cOMPanY WIll aSSuME nO rESPOnSIBIlItY FOr DaMaGE tO SIDInG, Etc. FrOM a POWEr
taBlE 1b: tanKlESS HEatEr ratInGS
"A"
"B"
"C"
KSZ065
3
0.65
79000
85.1
59000
246
17-3/8
8-5/16
6
KSZ075
3
0.75
90000
84.5
68000
283
17-3/8
8-5/16
6
KSZ100
3
1.00
119000
83.5
89000
370
17-3/8
8-5/16
6
KSZ090
4
0.90
110000
85.0
83000
346
22-3/8
10-13/16
7
KSZ125
4
1.25
149000
84.2
112000
467
22-3/8
10-13/16
7
KSZ150
4
1.50
177000
83.1
133000
554
22-3/8
10-13/16
7
KSZ120
5
1.20
147000
85.4
110000
458
27-3/8
13-5/16
8
KSZ175
5
1.75
207000
83.1
155000
646
27-3/8
13-5/16
8
KSZ200
5
2.00
235000
82.9
176000
733
27-3/8
13-5/16
8
I=B=R Net
Rating (Sq. ft)
AFUE (%)
I=B=R Net
Rating (Btu/hr)
Dimensions (inches)
Boiler Model
Number of
Sections
Burner
Input
(Gal/hr)
DOE Heating
Capacity
(Btu/hr)
MODEL
RATING (gpm)
KSZ065
2.25
KSZ075
2.25
KSZ100
2.50
KSZ090
2.50
KSZ125
2.75
KSZ150
3.00
KSZ120
2.75
KSZ175
3.25
KSZ200
3.50