Parameter Variable

Name Function

This network variable output is used to report the Space Comfort
humidity function’s status
Name Valid

value

local humidity level

0 to 100% RH

supply humidity level

0 to 100% RH

effective reset humid setpoint

0 to 100% RH

pi humid demand output

0 to 100% demand

Thermostat’s
I/O status

network output
UNVT_rh_status
nvoRHStatus

dehumid output active

0 = Dehumidification not active
1 = Dehumidification active

Setpoint network

output

SNVT_temp_p

nvoEffectSetpt

This output network variable is used to monitor the effective

temperature setpoint which may depend on nciSetpoints,
nvoEffectOccup, nviSetpoint and any local setpoint adjustment.
For example, if the occupancy state is unoccupied and the
heat/cool state is heat, the effective setpoint would be equal to
the unoccupied heating setpoint defined in nciSetpoints.

Valid Range: -40 to 100°F (-40 to 37.5°C)

Local setpoint
output

network output

SNVT_temp_p

nvoSetPoint

This output network variable is used to monitor the space

temperature setpoint

Valid Range : 40°F to 100°F (4.5°C to 37.5°C)

The present value is derived by the following

OccHeat Setpoint + ((OccCool Setpoint – OccHeat Setpoint ) / 2)