Viconics VT7607 Echelon Integration Guide User Manual

Page 8

Advertising
background image

8


Parameter Variable

Name

Function

Occupied
Cool & Heat
Setpoints

network Input
SNVT_temp_p
nviSetpoint

This input network variable is used to allow the occupied

temperature setpoints only to be changed via the network from a
single analog value. (Note: the Unoccupied setpoints are not
changed). The corresponding heating and cooling values are
derived from the minimum deadband configuration value

Default Null Value: 621.81°F (327.67°C or 0x7FFF)
Ex. If the minimum deadband configuration value = 2 °F and

nviSetpoint = 70°F.

• The resulting Occupied heating setpoint will equal 69 °F which is

derived from 70 °F minus ½ the minimum deadband configuration
value of 2 °F

The resulting Occupied cooling setpoint will equal 71 °F which is
derived from 70 °F plus ½ the minimum deadband configuration
value of 2 °F

This input network variable is used to set the time and date of the

Space Comfort Controller.

Default Null Value :

Sub

Name

Valid Range

Default Value

1

year

0 to 3000

0

2

month

0 to 12

0

3

day

0 to 31

0

4

hour

0 to 23

0

5

minute

0 to 59

0

Date and
time

network input
SNVT_time_stamp
nviTimeSet

6

second

0 to 59

0