Configuration Objects


The following SNVT and UNVT should be typically used for configuration purposes:

nciCfg1RtuHp;
nciSetpoints;
nciCfg3RtuHp;
nviDaySchedule[0]
nviDaySchedule[1]
nviDaySchedule[2]
nviDaySchedule[3]
nviDaySchedule[4]
nviDaySchedule[5]
nviDaySchedule[6]


Wiring Guide

Overview

For clarity we will use the term “Device” to represent any product with an active Echelon network
connection, including Viconics and non-Viconics controllers.

Summary Specifications:

Parameter

Details

Network Wiring

24 to 16AWG, twisted pair

Maximum total wire length

1

1600 feet (500 meters) in free topology

Maximum device-to-device distance

1600 feet (500 meters) in free topology

Polarity Polarity

insensitive

Multi-drop Free

Topology

Termination for Free Topology Network Segment

One RC network with Ra = 52.3

Ω±1%, 1/8W

Termination for Doubly Terminated Bus Network
Segment

Two RC network with Ra = 105

Ω±1%, 1/8W

Number of transceivers per segment

Up to 64

Baud rate

78000 bits per second

1

Network segment length varies depending on wire type.

Table 1: Summary of Specifications for a Viconics’ EIA-485 Network

Network Configuration

The Echelon network is designed to support free topology wiring and will accommodate bus, star, loop or
any of these topologies. Echelon devices can be located at any point along the network wiring.

Figures 3.1 to 3.5 present five different network topologies. The actual termination circuit will vary by