Viconics VT7607 Echelon Integration Guide User Manual

Page 13

Advertising
background image

13

Parameter Variable

Name

Function

fan mode

0 = On
1 = Auto
2 = Smart

0 = On

fan control

0 = Off
1 = On

1 = On

fan delay

0 = Off
1 = On

0 = Off

keypad lockout

0 = No_Lockout
1 = Level_1
2 = Level_2

No_Lockout

proportional band

2 to 8 F

2 F

temperature units

0 = °C
1 = °F

°F

frost protection

0 = Off
1 = On

0 = Off

temperature scale

0 = °C
1 = °F

°F

This configuration property defines the thermostat’s common

configuration parameters and their settings.

Valid Range and Default values:
Name

Valid Range

Default value

di1 configuration

0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service

0 = None

auxiliary contact
configuration

0 = NORMALLY_OPEN
1 = NORMALLY_CLOSE

0 =
NORMALLY_OPEN

number of events

2 or 4

2

progressive
recovery enable

0 = Off
1 = Active

0 = Off

number of heating
stages

1 = 1 Stage
2 = 2 Stages

2

number of cooling
stages

1 = 1 Stage
2 = 2 Stages

2

rh frontal display

0 = Off
1 = On

Off

humid low reset
temp

–40°F up to 15°F (-40°C
to –9.5°C)

-20.2°F (-29°C)

humid high reset
temp

20°F to 55°F (-6.5°C to
13°C)

32°F (0°C)

dehum lockout
temp

–40°F to 122°F (-40°C to
50°C)

32°F (0°C)

humidification high
limit setpoint

50% RH to 90% RH

85% RH

humid low reset rh
setpoint

10% RH to 90% RH

20% RH

dehumidification
hysterisys

2% RH to 20% RH

5% RH

rh sensor
calibration

–15% RH to 15% RH

0% RH

humidification
setpoint

10% RH to 90% RH

50% RH

dehumidification
setpoint

15% RH to 95% RH

70% RH

Thermostat’s
common
configuration
parameters
network input
config

UNVT_cfg_3_rtu_hp

nciCfg3RtuHp

dehumidification
lockout function

0 = Off
1 = On

1 = On