Specifications, Introduction – Winco ASCO 165 2-Wire User Manual

Page 3

Advertising
background image

3

SPECIFICATIONS

ENCLOSED AUTOMATIC TRANSFER SWITCH

Enclosure Size

Type 1

24” H x 14¼” W x 8” D

. . . . . . . . . . . . . . . . . .

(610 mm H x 362 mm W x 203 mm D)

Type 3R

25” H x 14¾” W x 8½” D

. . . . . . . . . . . . . . .

(635 mm H x 375 mm W x 216 mm D)

Weight Type 1 enclosure

67 lb

. . . . . . . . . . . . . . . . . . . . . .

Type 3R enclosure

82 lb

. . . . . . . . . . . . . . . . . . . . .

Temperature

Operating

–4˚ F to +122˚ F(–20˚ C to +50˚ C)

. . .

Storage

–67˚ F to +149˚ F(–55˚ C to +65˚ C)

. . . .

TRANSFER SWITCH

Poles

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Voltage (nominal)

220–240 V ac single phase

. . . . . . . . . .

Frequency (nominal)

60 Hz

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Current (depending upon the unit)

100 or 200 amps

. . . .

Withstand / Close–On Current

10,000 amps

. . . . . . . . . . . .

RMS Symmetrical amps 240 V ac max.

for any circuit breaker, manufacturer, or Type

per National Electrical Code, NEC/NFPA 70

Transfer Switch power terminals accept wire sizes

one #14 to 4/0 AWG AL or CU (copper)

CONTROLLER

Voltage (nominal)

220–240 V ac

. . . . . . . . . . . . . . . . . . . . . .

Pickup (source acceptable)

204 V ac

. . . . . . . . . . . .

Dropout (source unacceptable)

180 V ac

. . . . . . . .

Frequency (nominal) alternate (generator) source

60 Hz

.

Pickup (source acceptable)

57 Hz

. . . . . . . . . . . . . . .

Dropout (source unacceptable)

54 Hz

. . . . . . . . . . .

Generator control contacts

Start / Stop spdt 5 A max / 300 mA min at 30 V dc max.

terminals accept #22 to #14 AWG

stranded copper wire per terminal

Time Delays

Ignore preferred (utility) source outages

3 sec.

. . . . . . . .

Ignore alternate (generator) source outages

15 sec.

. . . .

Load transfer to alternate (generator) source

15 sec.

. . .

Load retransfer to preferred (utility) source

5 min.

. . . . . .

Generator cooldown period (after load retransfer) 1 min.

Automatic Generator Exerciser

Repeat time

every 14 days

. . . . . . . . . . . . . . . . . . . . . .

Duration

20 minutes

. . . . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

INTRODUCTION

ASCO Series 165 Automatic Transfer Switches are Listed

under the Underwriter’s Laboratories Standard for Transfer

Switch Equipment, UL–1008. They are intended for use only

in optional standby systems in accordance with the National

Electrical Code, NEC/NFPA 70, Article 702.
This automatic transfer switch is intended for standby power

applications in residential or light commercial use only.

The Series 165 Automatic Transfer

Switch is not for emergency or

life–support systems.

!

This product is not intended for emergency or

life–support systems.

If you have more stringent application requirements contact

ASCO for other products suitable for critical applications.

The automatic transfer switch helps provide safe

connection of the alternate source (generator) to the

electrical load after disconnecting the preferred source

(utility). It contains a double–throw, electromechanical

switching device for inherent isolation of the preferred and

alternate sources. This isolation prevents the danger of

connecting the utility to the generator which could cause

damage or personal injury. The automatic transfer switch’s

digital controller provides continuous monitoring of both

power sources and a start/stop signal to the generator.