Installation – Winco ASCO 165 2-Wire User Manual

Page 4

Advertising
background image

4

INSTALLATION

Installation of the ASCO Series 165 automatic transfer

switch must be performed by a licensed electrician. It must

be installed according to the National Electrical Code and

all local electrical code requirements. Refer to the

installation drawing and wiring diagram.

MALFUNCTION or SHORTENED LIFE

Protect the unit from construction grit and metal

chips to prevent malfunction or shortened life.

!

Remove the enclosure cover and inspect the unit for ship–

ping damage. If damage is evident do not install the unit. Type

1 enclosure is for indoor use only (refer to local codes for Type

4 use). Mount the automatic transfer switch vertically to a rigid

supporting structure. Level all mounting points with flat

washers behind the holes to avoid distortion of enclosure.

ELECTRICAL LINE CONNECTIONS

Installation wiring must be performed by a licensed

electrician in accordance with the National Electrical Code

(NEC) and all local electrical code requirements.
The automatic transfer switch must be protected by suitably

sized circuit breakers feeding the preferred and alternate

source terminals. The ratings of the circuit breakers must be

based on the requirements of the National Electrical Code

for its nameplate ampere and short circuit withstand ratings.

See the wiring diagram provided with the unit.

ELECTROCUTION HAZARD

Turn off utility power and turn off the

generator to prevent electrocution

when wiring the transfer switch.

CABLE SPACERS (200 amp. unit)

Three cable spacers are included with the 200 ampere size

transfer switch. Run the power cables through the cable

spacers as shown here and position the cable spacers

approximately 1½ inches from the terminal lugs.

cable spacer

cable spacers

1 ½ inch approximate

from terminal lugs

200 ampere transfer switch

requires cable spacers

L5

L1

L3 L7

L2

L6

preferred source (utility)

alternate source (generator)

load

CABLE LOOSENING DUE TO SHORT–CIRCUIT. Install

3 cable spacers 1½ in. from terminal lugs to prevent

cables from loosening in a short–circuit condition.

!

CABLE CONNECTIONS (see wiring diagram)

Prepare the wires for connection as follows: strip the

insulation; avoid nicking or ringing the conductors when

stripping the cable. Remove surface oxides from

conductors by cleaning with a wire brush. Apply electrical

joint compound and wipe away excess. Insert prepared

cable into lug and tighten the lug to the torque specified on

the rating label on the transfer switch.
Connect the preferred source (utility) line 1 and 2 wires to

the terminal lugs marked

L1 and L5 at the bottom. Connect

the alternate source (generator) line 1 and 2 wires to the

terminal lugs marked

L2 and L6 at the upper middle.

Connect the load line 1 and 2 wires to the terminal lugs

marked

L3 and L7 at the top of the transfer switch. Neutral

and ground terminals are provided.

GENERATOR STARTING CONTACTS

Before wiring the generator starting contacts refer to the

generator manufacturer’s installation manual for require-

ments. Make all connections to the controller with the gen-

erator battery disconnected. Verify that the ignition switch

is in the OFF position. Connect the generator starting con-

tacts to the appropriate terminals on terminal block TB7 on

the Controller (CP). See the wiring diagram provided with

the unit.
For wiring convenience terminal block TB7 has a removable

plug. Reconnect the plug with terminal screws facing inward.

CONTROLLER DAMAGE. Observe polarity when

connecting the generator battery to the controller.

Refer to wiring diagram. Be sure to reinstall the

TB7 block with terminal screws facing inward.

!

digital

controller

removable

terminal

block TB7

Be sure to

reinstall

with

terminal

screws

facing

inward.