3) Vacuum Switch – This boiler is equipped with a vacuum switch that is designed to prevent burner operation if the

combustion fan does not operate properly or there is a blockage in the vent system. This switch “makes” (permits
burner operation) as the vacuum increases. Figure 40 shows the correct method of reading the switch vacuum. The
vacuums in Table 9 are the minimums required for reliable operation. After the boiler fires, the vacuum will drop for
several minutes before stabilizing. The vacuum shown under “Burners On” in Table 9 is the minimum reading which
should be observed after the vacuum has stabilized. The Table 9 readings correspond to sea level vacuum switch
settings. Consult your Crown representative for possible variations in settings at altitudes over 2000ft.























MODELS

BURNERS ON

BWF061, BWF095

-0.57

-0.51

BWF128, BWF162

-0.96

-0.89

BWF195, BWF229

-1.21

-1.14

TABLE 9: MINIMUM. VACUUM SWITCH

READINGS (in. W.C.)

DURING

PREPURGE