Bwf troubleshooting chart – Crown Boiler BWF061 User Manual

Page 45

Advertising
background image

44



























120 volts across

black and white

transformer

primary leads on

back of R8285 ?

Thermostat

calls for heat

Circulator

start?

* Power off
* Blown fuse or
tripped breaker
* Miswired or
loose electrical
connection in
120 volt line

120 volts across

circulator

connections?

* Loose connection in
t'stat or zone valve end
switch wiring
* Defective t'stat or zone
valve end switch
* T'stat or zone system
miswired-consult zone
valve or t'stat
manufacturer's
instructions.

N

Induced

draft fan

start?

120 volts

present?

24 volts present

across yellow

and orange

connections on

R8222?

* Boiler off on
high limit
* Defective
high limit

* Defective
R8222 relay -
see note 6 on
page 43.
* Socket not fully
seated on relay

Y

Y

N

N

Y

N

Y

N

START

Y

N

Y

24volts across R
and C on R8285

fan center?

* Defective
transformer.
Replace R8285.
See note 5 on
page 43

24 volts across

G and C on

R8285 fan

center?

* Seized or
defective
circulator

* Defective relay on
R8285 - see note 6 on
page 43
* Relay not fully seated
in socket
* Loose connection in
circulator wiring

Unplug fan and
check for 120 volts
across black and
white connections
on female half of
plug.

* Loose
connection at
fan plug or fan
capacitor
* Defective
capacitor
* Defective fan

24 volts

present across

yellow and

purple

connections on

R8222?

Reconnect fan

* Kinked or blocked
vacuum switch tubing
* Defective vacuum
switch

Wait 30-50

seconds

(prepurge)

Continued on

next page

N

Y

N

Y

N

Y

BWF Troubleshooting Chart

Caution: Read page 43 before attempting to use this chart