Fig. 9 — Capacity Control Module

(Gas Engine or Turbine Drive)

2.

Turn chilled water thermostat until design

chilled water temperature is maintained. Mark
thermostat at this position. If capacity control
vanes hunt, turn throttle range adjustment

counterclockwise in small increments until

hunting ceases. Chilled water thermostat may
require resetting.

Setting Operating Controls — Pneumatic

NOTE; if raachiiie has special pne^iipaiic con­

trols, follow the instructions supplied in the job

data for their setting and adjustment.

PILOT POSITIONER

MAIN AIR CONNECTION (25 PSIG)
STARTING POINT ADJUSTMENT NUT

LEVER ARM

FOLLOWER SPRING
PILOT AIR CONNECTION

(FROM CONTROL CENTER)

Preparation:

1. Place jumper between terminals (L^ and

2. Open 25 lb air supply valve.

3. Remove cover from pilot positioner.

Calibration:

Rotate dial on chilled water thermostat to vary

pilot pressure. Observe pressure gage in pilot
supply line near pilot positioner and adjust starting

point nut (2) until piston operator (Fig. 4) begins

to move at 5 psi pilot pressure. Place follower
spring (4) in proper hole in level arm so that piston
operator opens 100% at 15 psi pilot pressure.

Completion:

1. Remove jumper from terminals [L^ and

2. Replace positioner cover.

ELECTRO-PNEUMATIC RELAY (Electric Motor
Drive Only)

SENSITIVITY SCREW

LOCKNUTS,

COVER

SET POINT SCREW

CONTROL AIR

(OUTPUT)

This control is factory calibrated to provide a

linear output signal of 3 psi at 6 volts d-c to 18 psi
at 15 volts d-c. Field recalibration should not be
necessary.

If calibration is required:

1. Establish 15 volt d-c input with 25 psi supply

air.

2. Turn sensitivity screw to obtain 18 psi or higher

output.

3. Adjust setpoint screw, if required, to set output

at 18 ± 1/4 psi.

4. Reduce input to 6 volts. Output should be 3 ±

1/4 psi. If low, turn sensitivity screw carefully

clockwise. If high, turn screw counterclockwise.

5. Re-check output at 15 volts. Repeat steps 3 and

4 if necessary.