Power. circuit, Ot, (g), Cuit light should go off – Carrier 17CB User Manual

Page 9: Press on-stop switch (light goes off)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

power.

circuit

POWER

ON

STOP

START

oT, (g) □

OIL

PUMP

SAFETY
CIRCUIT

3. Press ON-STOP button

(light on). If SAFETY

CIRCUIT light does not

^

go on, check resets on

^

condenser high-pressure
safety, cooler low refrig­
erant safety, bearing high temperature circuit

breaker, chilled water low temperature switch
and driver overload in starter. Check 3-amp
fuse in control center.

Manually trip and reset the bearing high

temperature circuit breaker, driver overload,
low refrigerant safety and chilled water switch
to be sure they cut off the safety light.

4. Press ON-STOP button

(light goes out). Remove

jumpers across terminals

(6^ and [0], [6^ and

5. Start chilled water and

condenser water pumps.

Press ON-STOP button
(light goes on).

POWER

ON

STOP

START

o

T

p

(|1 □

OIL

PUMP

SAFETY

CIRCUIT

■ ■ □

POWER

ON

STOP

START

OIL

PUMP

SAFETY
CIRCUIT

(g)

SAFETY

CIRCUIT

Turn on O I L - P U M P
switch for several seconds.
Pump should raise oil

pressure 25 to 27 psi
above refrigerant pressure
at machine shutdown con­
dition. SAFETY CIRCUIT light should go on.

If oil pump operates but SAFETY CIRCUIT
light is out, check water flow switches.

7. Turn off OIL PUMP

switch. SAFETY CIR-

POWER

ON

START

CUIT light should go off.

OIL

PUMP

SAFETY

CIRCUIT

8.

With OIL PUMP switch
on, manually trip and
reset water pump switches.
SAFETY CIRCUIT light

should go off as each
switch is tripped. (Continuous operation of oil

pump is unnecessary during these checks.)

START

SAFETY

CIRCUIT

9. With OIL PUMP and

ON-STOP

switches

on,

and water pumps oper­
a t i n g , p r e s s machine

START button (gas or
steam supply turned ofO

10. T u r n off OIL PUMP

switch. Oil pump must
continue operating.

11. Open oil pump main dis-

connect.

Driver

circuit

control must de-energize.
Oil pump will remain on
for 3 minutes.

12. OIL PUMP light goes out.

(g

POWER

ON

STOP

START

o

T

p

(g)

OIL

PUMP

SAFETY

CIRCUIT

POWER

ON

STOP

START

o

T

p

(g) □

OIL

PUMP

SAFETY
CIRCUIT

13. Press ON-STOP switch

(light goes off).

POWER

ON

STOP

START

gl

OIL

PUMP

SAFETY

CIRCUIT

14. Remove all power. Restore gas or steam supply

to drive. Restore power.

CONDENSER

/

□ □

POWER ON

START

STOP

OFF^

SAFETY

OIL PUMP CIRCUIT

COOLER

REFRIG
TEMP
CUT-OUT

TIT“

= K8

o

CONDENSER
PRESSURE

CUT-OUT

ELAPSED

TIME
INDICATOR

Z

CAPACITY

CONTROL

MODULE

RELAY MODULE

I I I I I I i~Tn

\

CONDENSER

□ □

POWER ON

STOP

START

OFF

OIL PUMP

SAFETY

CIRCUIT

REFRIG
TEMP
CUT-OUT

ELAPSED
TIME

INDICATOR

RELAY MODULE

I I I I I I I T-|

ELECTRONIC CONTROL

PNEUMATIC CONTROL

Fig. 7 — Control Center Components