In case that a considerable leakage occurs and to stop the

vacuum pump will be necessary and add a small quantity
of Freon to the system, if vacuum should not be obtained

(pressure gauge can't fall to 1 atmosphere.), start the
refrigeration unit and find the leakage with the special
leak-finder. When the defective soldering point is visible,
re-do it after opening the extension tube valve and
reestablishing the normal outside pressure inside the

group.

Because the melted alloy is sucked into the tubes and
block them, the pressure must be rebalanced when

vacuum is in the system in soldering. As soon as the
vacuum operation is over, add the quantity in grams of

R134a to the refrigeration system. Remember that every

system has an exact quantity of R134a with a tolerance of

±5 grams than can be added. (Figure 5)

Figure 5

Before performing this operation (if the vacuum pump and

refilling cylinder are connected), make sure that the valve
placed between the vacuum pump and refilling tube are
closed to keep the Freon for adding to the system. (Figure 6)

In addition, check the graduated scale on the cylinder for

the quantity of R134a to be added, for example, if we have

750 grams of Freon in the cylinder and must add 165
grams to the group, this amount will be reached when

R134a has dropped to 585 grams, remembering that the
indicator shows a lower limit of meniscus. Do this after

choosing the scale corresponding to the gas pressure
different scales reported as the same gas pressure

indicated by the pressure gauge on the top of the column.

To make R134a flow Into the system, open the valve

placed at the base of the cylinder and connected to the

filling tube. The amount of Freon cannot be added to the

system all at once because it may cause a blocking of
motor-compressor. Therefore, proceed by adding original
quantity of about 20-30 grams and close the valve

immediately.

The pressure rises and the motor-compressor must start,
sucking the gas and making the pressure go down again.

Regulate the valve again, maintaining the same manner

until reaching the quantity of R134a established for the
system being charged. When the system is running, the
suction pressure must be stabilized from 0.10 to 0.4
atmosphere.

-