selecting a location

Consider these points as you choose the location for your
humidifier.

Locate humidifier on supply air plenum (Fig. 1) or return air pie-

num. If the humidifier is installed on the return air plenum, the flex­

ible hose, round opening, is connected to the supply air plenum.

If furnace is equipped with air conditioning, humidifier should be

mounted above or at slope side of “A” coil to avoid possible splash­

ing (Fig. 2) of water.

Humidifier should be installed so that if the humidifier or any other

connections should leak, the resulting flow of water will not cause

damage. Under no condition is Sears and the manufacturer to be

held liable for any water damage in connection with this humidi­

fier. Never install humidifier in attic or crawl space where freezing

may occur or leaking will cause water damage.

If holes between supply air plenum and return air plenum must

be located more than 40 inches apart (Fig. 1), standard 6 inch

round pipe and fittings (not supplied) may be used, or an 8 foot

section of flexible tube No. 28115205 may be purchased through

the Sears parts department Materials needed for this type instaF

lation are available at Sears.

installation

The humidifier is shipped with the block-off panel on the
right side (Fig. 3). This is suitable for installation as shown

In Fig. 1, above. If this is suitable for your installation,
remove parts as shown under DISASSEMBLY.

If you require the block-off panel on the left side (Fig. 4),

start vrith DISASSEMBLY then remove block-off panel from

right flange and install with the same screws on left flange.

FIBER PLENUM DUCTS

NOTE: The mounting screws supplied are for stan­
dard installation on sheet metal plenum ducts.

If you have fiber plenum ducts, install the hu­
midifier and components with thru-bolts, nuts, and

washers (not supplied). (This fiber duct installa­
tion hardware is not supplied and must be pur­
chased from you local hardware store.)

CAUTION; Safety glasses should be worn to pre­
vent eye injury when installing humidifier.

disassembly

1. Take off front panel by sliding pan^ up and pulling out at

the bottom.

2. Remove corrugated spacer and by-pass boot which con­

tains damper, collar & flex tube and tube damp.

3. Remove media pad by lifting bottom edge up slightly and

pulling out.

^