Installation instructions (cont’d), Venting (cont’d) gas piping, Awarninc – Sears 153.33645 User Manual

Page 14: Awarnîng, Awarning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cont’d)

Venting (cont’d)

Gas Piping

All vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with
the new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal
screws.

TO

CHIMNEY

MIN, /, INCH

RISE PER LINEAR

FOOT

VENT PIPE INSTALLATION

AWARNINC

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

14 inches water column

'A

pound per square Inch (3.5kPa).

The minimum inlet gas pressure listed on the model rating
plate is for the purpose of input adjustment.

AWARNÎNG

If the gas control valve is subjected to pressures exceeding

'A

pound per square inch (3JkPa), the damage to the gas con­
trol valve could result in a fire or explosion from leaking gas.

There must be a minimum of 6" clearance between single wall
vent pipe and any combustible material. Fill and seal any clear­
ance between single wall vent pipe and combustible material
■with mortar mix, cement, or other noncombiistibie substance.

For other than single wall, follow vent pipe manufacturer’s clear­

ance specifications. To insure a tight fit of the vent pipe in a
brick chimney, seal around the vent pipe with mortar mix
cement.

AWARNING

Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.

AWARNING

Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach, and process chemicals are
typical compounds which are potentially corrosive.

AWARNING

If the main gas line shutoff serving all gas appliances is used,

also turn “OFF” the gas at each appliance. Leave all gas appli­
ances shut off until the water heater installation is complete.

A gas line of sufficient size must he run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA54 and the gas company con^
ceming pipe size.

There must ber

• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to help

prevent dlit and foreign materials from entering the gas control
valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water hearer. Use a soapy water solution, not a match or open
flame. Rinse off soapy solution and wipe dry.

Standard Models are for instaUation up to 3,300 feet above sea
level.

High Altitude Models

are for installation from 3,300 to 5,500

feet above sea level.
If a standard model is instaUed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input raring must be

reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Scars Service Center or gas utility for further
information.

14

Advertising
This manual is related to the following products: