Chromalox 8003 User Manual

Page 12

Advertising
background image

Chromalox 8003 User's Manual

9

SMART Function

SMART automatically determines the best PID control
parameters for your application.

To enable the SMART function, push the SMRT
pushbutton. The SMRT LED will light or flash according
to the algorithm automatically selected.

When the SMART function is enabled, it is possible to
display, but not to modify, the control parameters (PB,
TI, TD and rC).

When the traditional PID control is desired, push the
SMRT pushbutton again. The instrument maintains the
last set of SMART PID control parameters and enables
parameter modification.

Notes: 1. When ON/OFF control is programmed (PB = 0),

the SMART function is disabled.

2. The SMART enabling/disabling is protected by

security code.

Operator Mode

1. Remove the instrument from its case
2. Set the internal switch V2 in closed position
3. Re-insert the instrument
4. Switch on the instrument

V2

PZ1

PZ3

PZ4

PZ6

PZ7

PZ10

PZ11