Chromalox 8003 User Manual

Page 7

Advertising
background image

4

Chromalox 8003 User's Manual

General Operation

There are two setup modes for the 8003:

• Configuration Mode
• Operator Mode

In general, the Configuration Mode is the initial setup of
the controller when first installed. Input type and alarm
setup are examples of Configuration Mode settings. The
Operator Mode includes settings that might be adjusted
frequently with daily control operations such as setpoints
and PID parameters.

Notes for Configuration Mode:

FUNC

= Stores the new value of a selected parameter

and increments to the next parameter.

SMRT

= Scrolls parameters back (in reverse order)

without storing the new parameter value.

▲ = Increases the value of the selected parameter.

▼ = Decreases the value of the selected parameter.

Configuration Procedure

1. Remove the instrument from its case.
2. Set the internal switch V2 (see the following

figure) in open position.

3. Reinsert the instrument in its case.
4. Switch on the instrument. “CNF” should be displayed

in the upper display.

Note: If "CAL" indication is immediately displayed,

press the

▲ pushbutton to return to the

configuration mode (CNF).

5. Push the FUNC pushbutton.

The lower display shows the parameter code while
the upper display shows the actual parameter value.

PZ1

PZ3

PZ4

PZ6

PZ7

PZ10

PZ11

V2

8003 Manual

4/27/06, 2:24 PM

4