6

Chromalox 8003 User's Manual

P9 = Alarm 1 Inhibit
Available only when P7 is different from 0.

OFF = inhibit disabled
ON = inhibit enabled

Note: The Alarm Inhibit disables the alarm action after a
setpoint change. At startup, it automatically enables the
alarm when the process temperature reaches the present
condition.

P10 = Alarm 2 Type

0 = Not provided

2 = Band alarm

1= Process alarm

3 = Deviation alarm

P11 = Alarm 2 Operative Mode
Available only when P10 is different from 0.

H = High Alarm

L = Low Alarm

P12 = Alarm 2 Inhibit
Available only when P10 is different from 0

OFF = Inhibit disabled
ON = Inhibit enabled

Note: The Alarm Inhibit disables the alarm action after a
setpoint change. At startup, it automatically enables the
alarm when the process temperature reaches the present
condition.

P13 = Type of OFFSET Applied to the Measured Value

P13 = 0 = constant OFFSET (P14) all over the range
P13 different from 0 = P13 shows the application point
of the offset value set by P14 parameter.

P14 = OFFSET Value
When P13 = 0, P14 is programmable, in engineering
units, from -20 % to +20 % of the input range.

When P13 is different from 0, P14 is programmable from
-20 % to + 20 % of P13 value.

P13 = 0

Real curve

Readout

Adjusted
curve

P13

Real curve

Adjusted curve

Readout

P14

Input

P14

Input

-20% to +20%

8003 Manual