Chromalox 8003 User's Manual

5

P1 = Input Type and Standard Range

Range

0

= TC type

L

0 / +800 °C

1

= TC type

J

0 / +800 °C

2

= TC type

K

0 / +999 °C

3

= TC type

N

0 / +999 °C

4

= RTD type

Pt 100

-199 / +500 °C

5

= RTD type

Pt 100

-19.9 / +99.9 °C

8

= TC type

L

0 / +999 °F

9

= TC type

J

0 / +999 °F

10

= TC type

K

0 / +999 °F

11

= TC type

N

0 / +999 °F

12

= RTD type

Pt 100

-199 / +999 °F

P2 = Initial Scale Value
Not present when P1 = 5
The initial and full scale values are used by the PID
algorithm to calculate the input span.

P3 = Full Scale Value
Not present when P1 = 5
The initial and full scale values are used by the PID
algorithm to calculate the input span.
Note: the minimum input span (P3 - P2) is 300°C or
600°F for TC input and 100°C or 200°F for RTD input.

P4 = Output Configuration

H = Heating

HC = Heating / cooling

P5 = Heating Output Type

rEL = Relay
SSr = SSR

The output type selected here must match hardware
jumper setup (see page 2).

P6 = Cooling Element
Available only when P4 = HC

AIr = Air
OIL = Oil
H2O = Water

P7 = Alarm 1 Type
Available only when P4 = H

0 = None
1 = Process alarm (absolute)
2 = Band alarm (+ and - deviation)
3 = Deviation alarm

P8 = Alarm 1 Operation
Available only when P7 is different from 0

H = High Alarm

L = Low Alarm

(outside if band alarm) (inside if band alarm)

8003 Manual