2, Check output voltage of transformer secondary side SEC2

and SECl. Be sure transformer output is around 24 vac. If
tráíisfoTOjef output is zero vac and transformer is! receiving
correct input voltage (208v or 240v), then transformer

needs to be replaced with recommended transformer. If

transfoirtier output is 24 vaCj proceed to items 3 and 4,

3. Check Jow-voltage fuse shown in Fig. 6. If fuse is blown,

replace it. The transfortner cannot supply power to board

with fuse blown or loose. If fuse blows when unit has power
applied to it, the system most likely has 1 of the following

problems:

a. Check control circuit for a short or miswiring problem,

b. The maximui» load on transformer is 40 va. If load on

transformer is excessive, the low-voltage 5-amp firse
will blow to protect transfomicr. If load exceeds va

rating of transformer, a larger va rated transformer needs
to be installed. Check sequencers for excessive current
draw.

c. Check wiring of heaters. If a heater is miswirsd, fuse

may blow, if a heater is mis wired, correct miswiring.

4.

Check Tl, T2, and T3 connections on primary side of

transformer. If they are not connected properly, low-voltage
terminal board cannot supply 24-v signal to energize fan

motor. If transformer is receiving correct primary voltage
but is not putting Out correct secondary voltage, transformer

needs to be replaced,

B,

If Electric Heat Stages Will Not Turn On But Fan WIN

Turn On:

1. Check wiring of sequencers. Pay particular attention to

high- and low-voltagB wiring of sequencers.

2. Check plug wiring to make sure that it is wired correctly,

3. Check voltage to sequencer.

Sequencer

number 1 receives a

24-vac signal. If it is receiving correct voltage, cheek to see

if sequencer is closing. If sequencer is not dosing but is

10-