I. problems affecting txv, A. low suction pressure, B. high suction pressure – Bryant FA4A User Manual

Page 15: Piston body cleaning or replacement, Liquid tube strainer, Coiucondensate pan removal and replacement, I. a-coil units, Piston body cleaning or repl^'cement -16, Utc tech pub

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

A D G / 1 4 / 2 0 0 8 / T H U 0 3 :

UTC TECH PUB

F A X N o , 3 1 7 2 4 0 5 6 6 2

P , 0 1 5

The standard TXV is a bi-flow meterijig device that is used in

condensing and heat pump systems to adjust to changing load

conditions by maintaining a preset superheat temperature at outlet
of evaporator coil. The volume of refrigerant metered through
valve scat is dependent upon the following:

1. Superheat temperature sensed by sensing bulb on suction

tube at Outlet of evaporator coil. As long as this bulb
contains some liquid refrigerantj this temperature is con­

verted into pressure pushing downward on the diaphragm,

which opens the valve via push rods,

2. The Suction pressure at outlet of evaporator coil is trans­

ferred via the external equalizer tube to underside

of

diaphragm.

3. The needle valve On pin carrier is spring-loaded, which also

exerts pressure on underside of diaphragm via push rods,

which doses valve. Therefore, bulb pressure equals evapo­

rator pressure at outlet of coil plus spring pressure. If load
increases, temperature increases at bulb, which increases

pressure on topside of diaphragm, which pushes pin carrier
away from seal, opening valve and increasing flow of

re:frigerant. The increased refrigerant flow causes increased

leaving evaporator pressure which is transferred via the

equalizer tube to underside of diaphragm, with which the

pin carrier spring pressure closes valve. The refrigerant
flow is effectively stabilised to load demand with negligible

change in superheat.

The bi-flow TXV is used on split system heat pumps. In cooling
mode, TXV operates the same as a standard TXV previously
explained. However, when system is switched to heating mode of
operation, refrigerant ,flow is reversed. The bi"flow TXV has an
additional internal cheeje valve and external tubing. These addi­

tions allow refrigerant to bypass TXV when refrigerant flow is
reversed with only a 1- to 2-psig pressure drop through device.
When heat pump switches to defiost mode, refrigerant flows
through a completely open (not throttled) TXV, The bulb Senses

the residual heat of outlet tube of coil that had been operating in
heating mode (about S5“F and 155 psig). This temporary, not
throttled valve, decreases indoor pressure drop, which in turn .

increases refrigerant flow rate, decreases overall defrost time, and
enhances defrost efficiency.

I.

PROBLEMS AFFECTING TXV

A. Low Suction Pressure

1. Restriction in TXV

2.

Low

refrigerant charge

3. Low indoor load

4. Low evaporator airflow

B.

High Suction Pressure

1. Overcharging

2, Sensing bulb not secure to vapor tube

3, High indoor load

4. Large evaporator face area

When installing or removing TXV, wrap TXV with a wet cloth.
When reattaching TXV, make sure sensing bulb is in good thermal
contact with suction tube.

PISTON BODY CLEANING OR REPLACEMENT

A

CAUTION; Do not vent refrigerant to atmosphere. Re^

cover during system repair or final unit disposal.

CAUTION:

Damage may occur to the scroll compressor

A

if operated at a negative suction pressure during a system

pumpdown.

1. Pump down outdoor unit. Close service valves at outdoor

unit.

2. Recover remaining refrigerant from tubing and coil through

gage port On vapor-tube service valve.

3. Disconnect refrigerant (liquid) tube from piston body, (See

Fig. 13.)

4. Avoid damaging seal ring or machined surfaces on piston,

bore, and retainer.

5. Using small wire with a hook on end of it, remove piston

from body.

A

A93530

Fig. 13—Refrigerant Flow-Control Device

(For FA, FB, and FF)

CAUTION: When cleaning the pi?ton orifice, be careful

not to scratch or enlarge the opening, as this will affect

operation.

6. Install new or cleaned piston into body.

7. Replace seal ring on retainer.

S. Reconnect refrigerant tube to piston body,

9. Pressurize tubing and coil, then leak check.

10. Evacuate tubing and, coil as necessary.

A

CAUTION:

Use a backup wrench and do not over

tighten, as deformation of the piston body will occur,

Causing the piston to lodge in a partially open or closed

position.

LIQUID TUBE STRAINER

The TXV and refrigerant flow-control device is protected on the
indoor coil by a wire mesh strainer. It is located inside the 3/S-in.
liquid tube at field braze joint just outside unit casing. Access to

strainer is through field braze joint.

COIUCONDENSATE PAN REMOVAL

AND

replacement

I. A-COIL UNITS

If it is determined that system does not have leaks and refiigerant

is not contaminated, proceed as follows:

1, Recover system refrigerant.

^

15

-