Specifications-units with electric heater – Bryant 517G User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SPECIFICATIONS-UNITS WITH ELECTRIC HEATER

I MODEL

517Б

SIZE

N060015

I

PD60015

I

P060D18'

N060020

P060025I

Р060030И

RATINGS & PERFORMANCE

Nominal Capacity (Btuh)*

60,000

60,000

60,000

60,000

60,000

60,000

Nominal Airflow (Ft^/Min)t

2000

2000

2000

2000

2000

2000

Electric Heating Output (KW)t

15.0

15.0

18.0

20.0

25.0

30,0

Electric Heating Capacity (MBtuh)f:

38.5/47.0

38.5/47.0

46.1/56.4

51.3/62.7

64.1/78.4

76.9/86.0

ELECTRICAL ■ ■ ■ ' '

Unit Volts—Phase (60 Hz)

208/230-1

208/230-3

208/230-3

208/230-1

208/230-3 1 208/230-1 ■

208/230-3 1 208/230-1 ■

Operating Voltage Range

187-253

187-253

187-253

187-253

187-253

187-253

Internal Circuit Protection**

Fuses

CBtt

None

None

Fuses

CBtt

Fuses

Fuses

Single-Circuit Operation

Rated Load Amps

59.6/65.6

36.8/40.3

43.2/47.2

77.6/85.6

_

57.6/63.3

95.6/105.6

68.0/74.9.

113.6/125.6

Minimum Ampacity for Wire Sizing

74.5/82

-

46/50.4

54/59

97/107

72/79.1

119.5/132

85/93.6

142/157

Minimum Wire Size***

6/4

-

6/6

6/6

3/2

4/4

1/0

3/3

0/00 ■

Maximum Wire Length (Ft)***

77/122

__

152/154

130/132

118/149

-

154/155

153/192

165/166

161/203

Maximum Fuse Size (Amps)

80/90

50/60

60/60

100/110

-

80/80

125/150

90/100

150/175

Dual-Circuit Operation

Rated Load Amps L1 & L2

41.6/45.6

_

_

41.6/45.6

_

_

L 3 & L 4

18/20

-

-

36/40

-

-

Minimum Ampacity for Wire Sizing

LI &L2

52/57

52/57

_

_

L 3 & L 4

22.5/25

_

-

45/50

_

-

Minimum Wire Size*** LI & L2

6/6

-

-

6/6

-

-

L 3 & L 4

10/10

-

-

8/6

-

-

Maximum Wire Length (Ft)*** LI & L2

110/111

-

-

110/111

-

-

L 3 & L 4

102/102

-

-

81/126

-

-

Maximum Fuse Size (Amps) L1 & L2

60/60

-

-

60/60

-

-

L 3 & L 4

25/25

-

-

45/50

-

-

Control Transformer—24V (VA)

60

60

60

60

60

60

INDOORCOIL

Rows & Fins Per Inch

4 & 1 2

Height X Width (In.)

32.5 X 22.8

Face Area (Sq Ft)

5.1

R-22 Refrigerant Metering Device

Check-Flo-Rater

Piston ID Number

88

Condensate Drain Connection (Pri-Sec)

3/4 MPT-3/4 FPT

INDOOR BLOWER & MOTOR

Wheel Diameter x Width (In.)

1 1 x 9

Filter Size—Cleanable (In.)

2 0 x 2 5 x 1

Blower Motor HP

3/4

Blower Motor Speeds & Type

3 & DD (PSC)

Rated Load Amps

5.6

OPTIONAL EQUIPMENT (P/N’S)

Liquid-Tube Swivel Ell (3IS)tt

P651-1066

Vapor-Tube Swivel Ell (3/4)tt

P651-1068

Single-Circuit Kit**

301820-4001 1 = 1 = 1 301820-4001 ] = |

*See condensing unit or heat pump outdoor section PDS for cooiing and/or heating capacity ratings with 517G Fan Coils.
tSee air delivery table in this PDS.
tKW values shown are nominal rated heater outputs at 240V and do not include blower motor heat. Capacity values shown are calculated using KW

outputs at 208V/230V.

♦♦Single-phase 10-, 15-, 20-KW electric heaters have the internal circuit protection options shown. Single-phase 12-, 15-, or 20-KW heaters are

wired for dual-circuit operation. The optional single-circuit kit may be field-installed in units with a 12-, 15-, or 20-KW single-phase fused heater for
single-circuit operation.

tfCB = circuit breakers.
ttUsed for right-angle refrigerant connections to the coil.

♦♦♦Wire sizes and lengths are based on copper conductor at 86 ° F (30 ° C) ambient temperature.and ampacity shown in table. Insulation must be 90 ° C

on conductor used between the disconnect switch and the heater and at least 75 °C on the conductor used between the disconnect and the serv­
ice panel. If other than copper conductor is used, or if ambient temperature is above 86° F, determine wire size from ampacity shown and the Na­
tional Electrical Code. Wire lengths shown are measured one way along the wire path between the disconnect and service panel for minimum 2%
voltage drop.

■Units with 25- and 30-KW electric heaters are wired for 3-phase operation. These units are field-convertible for single-phase operation by moving

two factory high-voltage wires.

SSC-70