Cancels: 39585DP26-A

39585DP26-B

7/15/79

Model 585B Gas/Electric Units are fully self-contained,

single-packaged combination heating/cooling horizontal-

discharge units.

These packaged units are equipped with an energy-saving

RELITE-type electric spark ignition pilot that saves gas by

operating only when the room thermostat “calls for heat­

ing.” Natural gas controls are standard. For propane opera­

tion, conversion kit P/N 301625-703 must be field-installed.

Model 585B units have two A.G.A.-certified heating input

ratings. See Table I.

These units are designed for outdoor installation either on a

rooftop or at ground level on a slab. The cooling section is

factory-charged and sealed, minimizing installation time.

Installation is easy—connect gas supply, air ducts, conden­

sate drain, high- and low-voltage wiring, and install the air

filter.

NOTE:

An optional condenser coil grille is available for field

installation. See Figure 1.

A full line of rooftop system accessories are available for

field installation. These accessories include plenums with

factory-supplied high-capacity filter and outside air intake

hood, unitized curbs, economizers (both downflow and

horizontal), barometric relief dampers, concentric diffuser

box assemblies, flexible duct packages, and high-capacity

filter racks with filters. When installing these accessories,

see Installation Instructions packaged with them.

fmportant—Read Before Installing

1. Check all local or other applicable codes for information

concerning proximity to property lines, height above

roof, obstructions, etc.

2. Make certain power supply available (volts, hertz, and

phase) corresponds to that specified on unit rating plate.

3. Check electrical supply provided by utility to be sure

that service capacity is sufficient to handle load imposed

by this unit.

4. Locate the unit where the vent cap is a minimum of 4

feet from openable windows or doors.

5. The installation must conform with local building codes

or, in the absence of local codes, with the National Fuel

Gas Code ANSI Z223.1.

GENERAL

The condensing section has been designed and tested in ac­

cordance with ARI 210. The appliance design is certified by

American Gas Association for use with natural or propane

gases with appropriate controls and orifices.

Installation of the unit consists of the following:

I. Moving and Setting Unit In Place

II. Venting

III. Gas Piping

A77017

Figure 1—Sizes 024075, 030075, &

036075 With Optionai Condenser

Coii Griile instaiied

IV. Duct Connections

V. Electrical Connections

VI. Preparing Unit for Startup

VII. Heating Startup and Adjustments

VIII. Cooling Startup and Adjustments

IX. Care and Maintenance

I. MOVING AND SETTING UNIT IN PLACE

CAUTION:

Be sure to protect the top and sides of the unit

when rigging the unit to be lifted. See Figure 4.

Extreme caution should be used to prevent damage when

moving the unit. The unit should remain in an upright posi­

tion during all rigging and moving operations. To facilitate

lifting and moving, place the unit in an adequate rope or

cable sling.

A. Rooftop Installation

Place the unit on a level base. See Figures 8 and 9 for typical

installations. On flat roofs, be sure that the unit is at least 4

inches above the roof to prevent flooding. Consult local codes

for installation requirements. Be sure the roof will support

the additional weight. See Figure 2 for weight information.

NOTE:

See the Installation Instructions packaged with the

accessory plenum and unitized curb when these system ac­

cessories are being installed.

B. Ground Level Installation

CAUTION:

Unit must be mounted level for proper conden­

sate drainage.

Place the unit on a level concrete slab that is a minimum of

BDP Company, Division of Carrier Corp.