Measuring manifold pressure, C. adjusting gas input (propane gas furnace), D. adjusting burner air shutters – Bryant 585B User Manual

Page 9: E. blower fan relay (heating)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TABLE V-RATED GAS INPUTS (Btuh) FOR VARIOUS MAIN

BURNER ORIFICES AT INDICATED MANIFOLD PRESSURES*

585B

Size

Number

of

Orifices

Manifold

Pressure

(in. wc)

Natural Gas

Propane Gas

Orifice

P/N

Heating

Input

(Btuh)t

Orifice

P/N**

Heating

Input

(Btuh)t

Nat

Prop.

018050

& 024050

2

3.5

10.5

55365-451

40,000

55365-55

40,000

55365-42

50,000

55365-53

50,000

024075, 030075,

& 036075

3

3.5

10.5

55365-45Ф

60,000

55365-55

60,000

55365-42

75,000

55365-53

75,000

042100

4

3.5

10.5

55365-441

80,000

55365-55

80,000

55365-41

100,000

55365-53

100,000

036125,048125,

& 060125

5

3.5

10.5

55365-441

90,000

55365-55

90,000

55365-41

125,000

55365-53

125,000

060150

6

3.5

10.5

55365-441

120,000

55365-55

120,000

55365-41

150,000

55365-53

150,000

*Data in this tabie is based on aititudes from sea ievei up to 7000 feet above sea ievel at the minimum rated input, or 2000 feet above sea

levei at the maximum rated input. For higher altitudes, follow the recommendations of national and local codes,

t Gas inputs for natural gas are based on a heating value of 1050 Btu/Ft® with a specific gravity of 0.65 at the factory-set manifold pres­

sure of 3.5 inches wc. Gas inputs for propane gas is based on a heating value of 2500 Btu/Ft® with a specific gravity of 1.5 at a manifold
pressure of 10.5 inches wc.

fThese natural gas burner orifices are the factory-supplied orifices. All other natural gas orifices shown are optional field-supplied

orifices.

**Propane burner orifice P/N’s shown are furnished in conversion kit P/N 301625-703.

a. Determine number of seconds for gas meter test dial

to make one revolution.

b. Divide 3600 by number of seconds in step a.

c. Multiply result of step b by the nuinber of cubic feet

shown for one revolution of test dial. This gives

cubic feet of gas flow per hour.

d. Multiply result from step c by Btu heating value of

gas. Consult local utility for heating value of gas.

This is the total measured input in Btuh. Compare this value

with input shown in Table V.

Example:

Suppose the size of test dial is 1 cubic foot; it

takes 30 seconds to complete one revolution; heating value

of gas 1050 Btu/ft^. Proceed as follows:

a. 30 seconds to complete one revolution.

b. 3600 divided by 30 equals 120.

c. 120 times 1 equals 120 cubic feet of gas flow per

hour.

d. 120 times 1050 equals 126,000-Btuh input.

If the desired input was 125,000 Btuh, only minor changes

would have to be made at the pressure regulator adjustment

screw on the gas valve to bring the unit to the desired input.

If the measured input does not agree with the value desired,

the manifold pressure may be adjusted with the REG ADJ

screw on the gas valve as follows:

To increase input: Turn screw clockwise.

To decrease input: Turn screw counterclockwise.

2. Measuring Manifold Pressure

A water manometer is required to measure the manifold

pressure. If a spring manometer is used, make sure the

manometer is calibrated.

When the heating value of the natural gas being used for a

particular installation is significantly more or less than

1050 Btu/ft®, or slight manifold pressure changes are neces­

sary for other reasons, the manifold pressure may be

adjusted at the REG ADJ screw on the gas valve.

CAUTION:

Do not adj ust the manifold pressure more than

0.3 inches wc above or below the 3.5 inches wc factory set­

ting. If larger adjustments are required, change the burner

orifices following the recommendations of national and local
Proceed as follows to measure manifold pressure and to

adjust gas input:

a. Turn off gas to unit.

b. Remove pipe plug on gas valve outlet identified as

PRESS TAP, and connect manometer at this point.

c. Turn on gas to unit and start heating section.

d. With all burners fired, adjust manifold pressure

with REG ADJ screw on gas valve to obtain desired

gas input.

NOTE:

To increase input, increase manifold pressure by

turning screw clockwise. To decrease input, decrease

manifold pressure by turning screw counterclockwise.

e. Turn off gas to unit. Remove manometer from gas

valve and replace pipe plug.

C. Adjusting Gas Input (Propane Gas Furnace)

The field-installed propane conversion kit contains a pro­

pane gas regulator spring that replaces the natural gas reg­

ulator spring in the unit combination gas valve/pressure

regulator. The converted pressure regulator is then adjusted

to provide the desired gas input. Follow the procedures in

the conversion kit Installation Instructions to adjust the

propane gas input.

D. Adjusting Burner Air Shutters

To adjust the primary air to each burner, partially close the

air shutter until there is a slight yellow tip on the top of the

flame, then open the air shutter until the yellow tip just dis­

appears. This should be done after the burners have been

operating at full input for 5 or 10 minutes (approximately).

Secure shutters with locking screws after adjusting primary

air to each burner.

E. Blower Fan Relay (Heating)

The heating relay (See Figure 7) is located in the control box

and is adjustable to permit lengthening or shortening the

“off” cycle. The “on” cycle is automatically adjusted as the

“ofiT’ cycle is changed.

The fan control adjusting lever is factory-set at the center

position and should give optimum performance in most in­

stallations. However, on unusual installations, or where the

line voltage is considerably above or below the rated output,

it may be necessary to increase or decrease the length of

time the blower remains on. For longer blower operation,

move the adjusting lever toward the right-hand position. In

this position, the control makes contact sooner and takes the

maximum time to break contact. For shorter blower opera­

tion, move the lever to the left-hand position.

-9-