B. low-voltage connections, C. heat anticipator setting, Vi. preparing unit for startup – Bryant 585B User Manual

Page 8: Vii. heating startup and adjustments, A. gas input, B. adjusting gas input (natural gas furnace), Measuring gas flow at meter

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

NOTE:

On 3-phase units, the third power lead is connected

to the brown high-voltage pigtail lead. See unit wiring label

and Figure 11.

B. Special Procedures for 208-V Operation

WARNING:

Make sure the power supply to the unit is

switched OFF before making any wiring changes.

When size 018050 thru 036125 dual-voltage units are to be

operated at 208 volts, unplug the orange lead running to the

primary side of the unit transformer and plug it onto the

208-V red transformer tap. See the unit wiring label.

When sizes 018050 or 024050 are to be operated at 208 volts,

additional wiring changes must be made in the unit control

box as follows:

1. Unplug orange motor lead connected to evaporator mo­

tor run capacitor (4A1). See unit wiring label. Tape end

of orange lead.

2. Plug unused yellow motor lead onto vacated run capaci­

tor terminal. Figure 12 shows corrected wiring.

B. Low-Voltage Connections

CAUTION:

When room thermostat leads are run in the

same conduit with high-voltage leads, they must be insu­

lated for the highest voltage contained within the conduit.

A room thermostat with isolated contacts must be used to

prevent interconnection of class 2 outputs. (The following

recommended thermostats meet this criteria.)

Recommended room thermostats are P/N 34427D03O (sub­

base included) or P/N PS2758-1 (or -2) with subbase P/N

PS2759-34 for manual system changeover. For automatic

system changeover, use thermostat P/N 34427D52 or P/N

PS3108A with subbase P/N PS3109E.

Mount the room thermostat on an inside wall of the space to

be conditioned. The thermostat should be positioned approx­

imately 4 or 5 feet above the floor, and located where it will

not be subjected directly to either a cooling or heating

source, or direct exposure to sunlight.

If low-voltage leads from the thermostat are run separately,

enter the unit through grommeted hole provided in the con­

trol corner panel. See Figure 2 for hole location.

Connect the low-voltage thermostat leads to the flagged pig­

tail leads that run through a hole in the bottom of the unit

control box. See Figures 7 and 11.

NOTE:

Connect thermostat to unit using No. 18 AWG “col­

or-coded” insulated wires. If thermostat is located more than

100 feet from unit as measured along the low-voltage wires,

use No. 16 AWG wire.

C. Heat Anticipator Setting

The room thermostat heat anticipator must be properly

adjusted to insure proper heating performance. Set the heat

anticipator to 0.85 amps.

Failure to make a proper heat anticipator adjustment will

result in improper operation, discomfort to the occupants of

the conditioned space, and inefficient energy utilization;

however, the required setting can be changed slightly to pro­

vide a greater degree of comfort for a particular installation.

VI.

PREPARING UNIT FOR STARTUP

Proceed as follows to prepare the unit for startup:

1. Remove all service access panels and check for shipping

damages, such as broken lines, loose parts, disconnected

wires, etc.

2. Read and follow instructions on all WARNING, CAU­

TION, AND INFORMATION labels and tags attached

to unit; such as motor rotation labels, blower rotation

labels, and vent instruction tag.

3. Make certain gas supply has been purged and all gas

piping checked.

WARNING:

Do not purge into the combustion chamber. Do

not use a match or other open flame to check for leakage.

4. Check to be sure all wiring connections, including facto­

ry connections, have been completed and are tight.

5. Inspect all supply ducts and grilles to be sure they are

adjusted properly.

6. Check to be sure air filters are in place.

VII.

HEATING STARTUP AND ADJUSTMENTS

CAUTION:

Complete the steps in Section VI before starting

unit.

Do not jumper any safety devices when operating unit.

Burner orifice alignment must be insured. Unstable opera­

tion may occur when the manifold’s burner orifices are not

aligned correctly. To insure correct burner orifice alignment,

check the orifice angle with a machinist’s or carpenter’s

square, a machinist’s protractor, or other suitable device.

The orifice angle should be from horizontal to 3 degrees

down as measured from the unit base.

Follow the instructions on the unit rating plate for starting

the heating section.

A. Gas Input

The unit rating plate indicates two A.G.A.-certified gas

inputs. The burners are equipped with natural gas orifices

that deliver the minimum rated input. Optional field-in-

stalled burner orifices are required to provide the optional

maximum heating input rating. See Table V.

When the unit is being installed for operation at the

optional maximum heating input rating, proceed as follows

to install the field-supplied maximum heating input burner

orifices:

1. Remove burner shield and burners.

2. Remove factory-supplied burner orifices from manifold

and replace with field-supplied maximum heating input

burner orifices.

3. Replace burners and burner shield.

4. Mark appropriate changes on unit rating plate in boxes

provided.

For propane gas operation, propane conversion kit P/N

301625-703 must be field-installed. This kit contains six

burner orifices for the minimum input rating and six for the

maximum input rating. Six orifices are sufficient for the

largest heating unit. For smaller heating sizes, all orifices

will not be required. See Table V.

CAUTION:

The units are designed to give the correct input

using the fixed orifices and manifold pressures shown in

Table V. Do not redrill the orifices under any circumstances.

NOTE:

The minimum and maximum rated inputs shown in

Table V are for altitudes from sea level up to 7000 feet above

sea level at the minimum input or 2000 feet above sea level

at the maximum input. These inputs are based on a heating

value for natural gas of 1050 Btu/ft® at 0.65 specific gravity

and propane gas with a heating value of 2500 Btu/ft®. For

elevations above 7000 feet at the minimum rated input or

2000 feet at the maximum rated input, reduce the ratings

4% for each 1000 feet above sea level. For other gas heating

values or specific gravities, refer to BDP training and ap­

plication materials, national and local codes, or contact your

BDP Distributor or Branch to determine the required orifice

size.

B. Adjusting Gas Input (Natural Gas Furnace)

Natural gas input can be determined and adjusted using one

of the following two recommended methods.

1. Measuring Gas Flow at Meter

All other gas appliances must be turned off when measuring

gas flow at meter to check the input. Proceed as follows:

-8-

Advertising